Element Comm Status
BBV
R
BV:2999
element_stat_1
Element Communications Alarm
BALM
R
BV:105
comm_lost_alm_1
Emergency Stop
CBP
EMSTOP
W
0 to 1
BV:45
emstop_1
Equipment Alarm
CALM
R
BV:127
element_alarm_1
Equipment Touch reset linkage Alarm
BBV
0 to 1
Evaporator Discharge Tmp
CAP
EDT
R
°F
AV:76
edt_1
Exhaust Air Temperature
CAP
Exhaust Fan VFD Speed
CAP
EFAN_VFD
R
%
0 to 100
AV:2075
ef_vfd_output_1
Fan Fail Shuts Down Unit
CBP
SFS_SHUT
W
No
0 to 1
BV:50
sfs_shut_1
Fan Mode
CAP
FAN_MODE
R/W
1
0 to 1
AV:77
fan_mode_1
Filter Status Input
CBP
FLTS
W
0 to 1
BV:1052
filter_status_1
Fire Shut Down Emergency Mode (fire-smoke)
CALM
A404
R
BV:114
a404_1
Fire Shutdown Input
CBP
FSD
W
0 to 1
BV:1005
firedown_status_1
Freeze Status Switch
CBP
FRZ
W
0 to 1
BV:41
frz_1
Heat Interlock Relay
CBP
HIR
W
0 to 1
BV:1026
heat_interlock_relay_1
Heat Relay 1
CBP
HS1
R
0 to 1
BV:52
hs1_1
Heat Relay 2
CBP
HS2
R
0 to 1
BV:53
hs2_1
Heat-Cool Setpoint Gap
CAP
HCSP_GAP
R/W
°^F
2 to 10
AV:83
hcsp_gap_1
Heating Control Point
CAP
HEATCPNT
R
–10 to 140
AV:1025
heat_ctrl_point_1
Heating Supply Air Setpt
CAP
SASPHEAT
R/W
dF
85
80 to 120
AV:85
saspheat_1
High OAT Lockout Temp
CAP
OAT_LOCK
R/W
dF
60
–40 to 120
AV:9008
econ_oat_lockout_1
Hot Water Valve Position
CAP
Ht.Coil Command Position
CAP
HTCLCPOS
R
%
0 to 100
AV:55
htclcpos_1
HumidiMizer 3-way Valve
CBP
HUM3WVAL
R
0 to 1
BV:47
hum3wval_1
HumidiMizer Capacity
CAP
HMZRCAPC
R
%
0 to 100
AV:57
hmzrcapc_1
HVAC Mode Numerical Form
CAP
MODEHVAC
R
0 to 40
AV:1022
hvac_mode_1
IAQ - Discrete Input
CBP
IAQIN
W
0 to 1
BV:1050
iaq_status_1
IAQ - PPM Indoor CO2
CAP
IAQ
W
0 to 5000
AV:1009
iaq_1
IAQ Demand Vent Min.Flow
CAP
OACFMMIN
R/W
CFM
0
0 to 20000
AV:58
oacfmmin_1
IAQ Demand Vent Min.Pos.
CAP
Indoor Air CO2
BAV
LINK_IAQ
R
AV:2607
link_iaq_1
Leaving Air Temperature
CAP
LAT
R
dF
–40 to 240
AV:1027
lvg_air_temeprature_1
Linkage Max Damper Position
BAV
LINK_MAX_DMPR
R/W
AV:2611
link_max_dmpr_1
Local Machine Disable
CBP
UNITSTOP
W
0 to 1
BV:59
unitstop_1
Local Schedule
BBV
SCHEDULE
R
BV:5
schedule_1
Maximum Damper Position
BAV
Maximum Reset
BAV
Minimum Damper Position
BAV
Mixed Air Temperature
CAP
MAT
R
dF
AV:1500
ma_temp_1
OAQ - PPM Outdoor CO2
CAP
OAQ
R/W
0 to 5000
AV:113
oaq_1
Occupied Cool Mode End
CAP
OCCL_END
R
°F
0 to 100
AV:114
occl_end_1
Occupied Cool Mode Start
CAP
OCCLSTRT
R
°F
0 to 100
AV:115
occlstrt_1
Occupied Heat Mode End
CAP
OCHT_END
R
°F
0 to 100
AV:116
ocht_end_1
Occupied Heat Mode Start
CAP
OCHTSTRT
R
°F
0 to 100
AV:117
ochtstrt_1
Occupied Heating Enabled
CBP
HTOCCENA
W
No
0 to 1
BV:70
htoccena_1
Occupied?
CBP
OCCUPIED
W
0 to 1
BV:2008
occ_status_1
Outside Air CFM
CAP
OACFM
R
CFM
0 to 50000
AV:66
oacfm_1
Outside Air Relative Humidity
CAP
OARH
R/W
%
0 to 100
AV:119
oarh_1
Outside Air Temperature
CAP
OAT
W
dF
–40 to 240
AV:1003
oat_1
Post Filter Stat. Input
CBP
PFLTS_STATUS
RW
0 to 1
BV:72
pflts_status_1
Relay 3 W1 Gas Valve 2
CBP
HS3
R
0 to 1
BV:76
hs3_1
Relay 4 W2 Gas Valve 2
CBP
HS4
R
0 to 1
BV:77
hs4_1
Relay 5 W1 Gas Valve 3
CBP
HS5
R
0 to 1
BV:78
hs5_1
Relay 6 W2 Gas Valve 3
CBP
HS6
R
0 to 1
BV:79
hs6_1
Remote Alarm/Aux Relay
CBP
ALRM
W
0 to 1
BV:2014
aux_relay_1
Remote Input State
CBP
RMTIN
W
0 to 1
BV:81
rmtin_1
Requested Heat Stage
CAP
HT_STAGE
R
0 to 20
AV:2003
heat_run_1
Reset Limit
CAP
LIMT
R/W
^F
10
0 to 20
AV:131
limt_1
Reset Ratio
CAP
RTIO
R/W
3
0 to 10
AV:132
rtio_1
Return Air CFM
CAP
RACFM
R
CFM
0 to 50000
AV:69
racfm_1
Return Air Enthalpy
CAP
RAE
R
AV:133
rae_1
Return Air Relative Humidity
CAP
RARH
R/W
%
0 to 100
AV:134
rarh_1
Return Air Temperature
CAP
RAT
R/W
°F
–40 to 240
AV:135
rat_1
Return Air Thermistor Failure
CALM
Setpoint / Cooling Occupied Setpoint
BAV
Setpoint / Cooling Unoccupied Setpoint
BAV
Setpoint / Heating Occupied Setpoint
BAV
APPENDIX F
—
BACNET COMMUNICATION OPTION (CONT)
NETWORK POINTS LIST (cont)
POINT DESCRIPTION
TYPE
CCN POINT NAME READ/
WRITE UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...