Section 8. Operation
320
•
Where possible, run excitation leads and signal leads in separate shields
to minimize transients.
•
When measurement speed is not a prime consideration, additional time
can be used to ensure ample settling time. The settling time required
can be measured with the CR800.
•
In difficult cases, settling error can be measured as described in
Measuring Settling Time
(p. 320).
Measuring Settling Time
Settling time for a particular sensor and cable can be measured with the CR800.
Programming a series of measurements with increasing settling times will yield
data that indicate at what settling time a further increase results in negligible
change in the measured voltage. The programmed settling time at this point
indicates the settling time needed for the sensor / cable combination.
CRBasic example
Measuring Settling Time
(p. 320)
presents CRBasic code to help
determine settling time for a pressure transducer using a high-capacitance
semiconductor. The code consists of a series of full-bridge measurements
(
BrFull()
) with increasing settling times. The pressure transducer is placed in
steady-state conditions so changes in measured voltage are attributable to settling
time rather than changes in pressure. Reviewing
CRBasic Programming —
Details
(p. 119)
may help in understanding the CRBasic code in the example.
The first six measurements are shown in table
First Six Values of Settling Time
Data
(p. 321).
Each trace in figure
Settling Time for Pressure Transducer
(p. 321)
contains all twenty
PT()
mV/V values (left axis) for a given record number, along
with an average value showing the measurements as percent of final reading (right
axis). The reading has settled to 99.5% of the final value by the fourteenth
measurement, which is contained in variable PT(14). This is suitable accuracy
for the application, so a settling time of 1400 µs is determined to be adequate.
Measuring Settling Time
'This program example demonstrates the measurement of settling time using a single
'measurement instruction multiple times in succession. In this case, the program measures
'the temperature of the CR800 wiring panel.
Public
RefTemp
'Declare variable to receive instruction
BeginProg
Scan
(1,Sec,3,0)
PanelTemp
(RefTemp, 250)
'Instruction to make measurement
NextScan
EndProg
measures the settling time of a sensor measured with a differential
'voltage measurement
Public
PT(20)
'Variable to hold the measurements
DataTable
(Settle,True,100)
Sample
(20,PT(),IEEE4)
EndTable
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......