Section 7. Installation
268
d. Calculate RS
10
:
RS
10
= X
10
• Rf = 103900
6. Calculate RS
10
/RS
0
, K, and temperature:
a. RS
10
/RS
0
= 1.039
b. K = (RS
10
/RS
0
)-
1 = 0.039
c. T = g * K^4 + h * K^3 + i * K^2 + j * K = 9.99 °C
d. T = (SQRT(d * (R
S
10
/RS
0
) + e) -
a) / f = 9.99 °C
1
A Campbell Scientific terminal-input module (TIM) can be used to complete the resistive bridge
circuit. Refer to the appendix
Passive-Signal Conditioners — List
(p. 563).
4
Get this value from a PRT-resistance-to-temperature table
CRBasic Programs and Notes
PT100 BrHalf3W() Three-Wire Half-Bridge Calibration
'This program example demonstrates the calibration of a 100-ohm PRT (PT100) in a three-wire
'half bridge with voltage excitation. See previous procedure and schematic.
'Declare constants and variables:
Const
Rf = 10000000
'Value of bridge resistor
Public
X
'Raw output from the bridge
Public
RS0
'Calculated PT100 resistance at 0 °C
BeginProg
Scan
(1,Sec,0,0)
....'Measure X:
'BrHalf3W(Dest,Reps,Range,SEChan,ExChan,MeasPEx,ExmV,RevEx,SettlingTime,
' Integ,Mult,Offset)
BrHalf3W
(X,1,mV25,1,Vx1,1,2033,True,0,250,1,0)
'Calculate RS0:
RS0 = Rf * X
NextScan
EndProg
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......