Section 7. Installation
256
•
Active: 66 mA
•
Timeout: 15 s
Probes 1, 2, 3, and 4 are connected to SDI-12 / control port
C1
.
The time line in table
Example Power Usage Profile for a Network of SDI-12
Probes
(p. 256)
shows a 35 second power-usage profile example.
For most applications, total power usage of 318 mA for 15 seconds is not
excessive, but if 16 probes were wired to the same SDI-12 port, the resulting
power draw would be excessive. Spreading sensors over several SDI-12 terminals
will help reduce power consumption.
Example Power Usage Profile for a Network of SDI-12 Probes
Time into
Measuremen
t Process (s) Command
All
Probes
Awake
Time
Out
Expires
Probe 1
(mA
1
)
Probe 2
(mA
1
)
Probe 3
(mA
1
)
Probe 4
(mA
1
)
Total
mA
Sleep
0.25
0.25
0.25
0.25
1
1
1M!
Yes
120
66
66
66
318
2–14
120
66
66
66
318
15
Yes
120
66
66
66
318
16
1D0!
Yes
66
66
66
66
264
17–29
66
66
66
66
264
30
Yes
66
66
66
66
264
Sleep
0.25
0.25
0.25
0.25
1
1
Current use:
0.25 mA = sleep
66 mA = awake
120 mA = measuring
7.7.15 Compiling: Conditional Code
This feature circumvents system filters that look at file extensions for specific
loggers; it makes possible the writing of a single file of code to run on multiple
models of CRBasic dataloggers.
When a CRBasic user program is sent to the CR800, an exact copy of the program
is saved as a file on the
CPU: drive
(p. 407).
A binary version of the program, the
"operating program", is created by the CR800 compiler and written to
Operating
Memory
(p. 408,
This is the program version that runs the CR800.
CRBasic allows definition of conditional code, preceded by a hash character (#),
in the CRBasic program that is compiled into the operating program depending on
the conditional settings. In addition, all Campbell Scientific dataloggers (except
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......