Section 8. Operation
385
When connecting serial sensors to a
C
terminal configured as Rx, the
sensor power consumption may increase by a few milliamps due to
voltage clamps in the CR800. An external resistor may need to be added
in series to the Rx line to limit the current drain, although this is not
advisable at very high baud rates. See
Circuit to Limit C Terminal Input to
5 Volts
(p. 385).
FIGURE 91: Circuit to Limit C Terminal Input to 5 Vdc
8.1.6.2 SDI-12 Sensor Support — Details
Related Topics:
•
SDI-12 Sensor Support — Overview
(p. 74)
•
SDI-12 Sensor Support — Details
(p. 385)
•
Serial I/O: SDI-12 Sensor Support — Programming Resource
(p. 240)
SDI-12 is a communication protocol developed to transmit digital data from smart
sensors to data-acquisition units. It is a simple protocol, requiring only a single
communication wire. Typically, the data-acquisition unit also supplies power (12
Vdc and ground) to the SDI-12 sensor.
SDI12Recorder()
instruction
communicates with SDI-12 sensors on terminals configured for SDI-12 input.
See the table
CR800 Terminal Definitions
(p. 58)
to determine those terminals
configurable for SDI-12 communications.
8.1.7 Field Calibration — Overview
Related Topics:
•
Field Calibration — Overview
(p. 75)
•
Field Calibration — Details
(p. 214)
Calibration increases accuracy of a measurement device by adjusting its output, or
the measurement of its output, to match independently verified quantities.
Adjusting sensor output directly is preferred, but not always possible or practical.
By adding
FieldCal()
or
FieldCalStrain()
instructions to the CR800 CRBasic
program, measurements of a linear sensor can be adjusted by modifying the
programmed multiplier and offset applied to the measurement without modifying
or recompiling the CRBasic program.
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......