Section 7. Installation
237
Voltage Measurement Instruction Parameters for Dwell Burst
Parameters
Description
Destination
A variable array dimensioned to store all measurements from one input. For
example, the declaration,
Dim
FastTemp(500)
dimensions array
FastTemp()
to store 500 measurements, which is one second of
data at 500 Hz or one-half second of data at 1000 Hz.
The dimension can be any integer from
1
to
65535
.
Count
(was
Repetitions
)
The number of measurements to make on one channel. This number usually
equals the number of elements dimensioned in the
Destination
array.
Valid arguments range from
1
to
65535
.
Voltage Range
The analog-input voltage range to be used during measurements. No change from
standard measurement mode. Use any valid voltage range. However, ranges
appended with
C
cause measurements to be slower.
Single-Ended Channel
The single-ended analog-input terminal number preceded by a dash (
-
). Valid
arguments range from
-1
to
-
6.
Differential Channel
The differential analog input terminal number preceded by a dash (
-
). Valid
arguments range from
-1
to
-
3.
Measure Offset
No change from standard measurement mode. For fastest rate, set to
False.
Measurements per Excitation
Must equal the value entered in
Repetitions
.
Reverse Ex
No change from standard measurement mode. For fastest rate, set to
False.
Rev Diff
No change from standard measurement mode. For fastest rate, set to
False.
SampleInterval (was
SettlingTime)
Sample interval in µs. This argument determines the measurement rate.
• 500 µs interval = 2000 Hz rate
• 750 µs interval = 1333.33 Hz rate
Integ
Ignored if set to an integer.Arguments
_50Hz
and
_60Hz
are valid for ac rejection
but are probably not very useful in burst applications.
Multiplier
No change from standard measurement mode. Enter the proper multiplier. This is
the slope of the linear equation that equates output voltage to the measured
phenomena. Any number greater or less than
0
is valid.
Offset
No change from standard measurement mode. Enter the proper offset. This is the
Y intercept of the linear equation that equates output voltage to the measured
phenomena.
7.7.12.1 Tips — Fast Analog Voltage
•
In the preceding examples, the CR800 disables the auto self-calibration
to reach the stated measurement speeds. Disabling auto self-calibration
increases the risk of measurement errors, especially when the CR800 is
exposed to temperature swings.
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......