Section 8. Operation
438
Term: input registers 30001 to 39999
Hold values resulting from an analog measurement. Input registers in the
Modbus domain are read-only. In the Campbell Scientific domain, the
leading digit in Modbus registers is ignored, and so are assigned together to a
single
Dim
- or
Public
- variable array (read / write).
Term: holding registers 40001 to 49999
Hold values resulting from a programming action. Holding registers in the
Modbus domain are read / write. In the Campbell Scientific domain, the
leading digit in Modbus registers is ignored, and so are assigned together to a
single
Dim
or
Public
variable array (read / write).
Term: RTU / PLC
Remote Telemetry Units (RTUs) and Programmable Logic Controllers
(PLCs) were at one time used in exclusive applications. As technology
increases, however, the distinction between RTUs and PLCs becomes more
blurred. A CR800 fits both RTU and PLC definitions.
8.10.3.2 Programming for Modbus
8.10.3.2.1 Declarations (Modbus Programming)
Table
Modbus Registers: CRBasic Port, Flag, and Variable Equivalents
(p. 438)
shows the linkage between terminals configured for control, flags and Boolean
variables and Modbus registers. Modbus does not distinguish between terminals
configured for control, flags, or Boolean variables. By declaring only terminals
configured for control, or flags, or Boolean variables, the declared feature is
addressed by default. A typical CRBasic program for a Modbus application
declares variables and ports, or variables and flags, or variables and Boolean
variables.
Modbus Registers: CRBasic Port, Flag, and Variable
Equivalents
CRBasic Port,
Flag, or Variable
Example CRBasic
Declaration
Equivalent Example
Modbus Register
C
terminal configured
for control
Public Port(4)
00001 to 00004
Flag
Public Flag(17)
00001 to 00017
Boolean variable
Public ArrayB(56) as
Boolean
00001 to 00056
Variable
Public ArrayV(20)
1
40001 to 40040
1
30001 to 30040
1
1
Because of byte-number differences, each CR800 domain variable translates
to two Modbus domain input / holding registers.
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......