7 - 4
DIGITAL INPUT/OUTPUT MODULES
Edition 06.2005
7.1
Input/output module AEK / SEA (continued)
Technical characteristics
Outputs
Outputs
16
External supply voltage
min. 20V
the output blocks
max. 30V
Admissible permanent current
0,5A, 100% at the same time loadable
Visual check
by LED
Galvanic separation
over opto couplers
0V-Potential
internally separately in blocks to ever 8 outputs
Short circuit proof
Current limiting
Over-temperature disconnection
Internal cut-off diode for inductive loads
max. 200mJ
Fuse protection
ever 8 outputs over own inlet for separate
fuse protection
Output delay
approx. 7,5µs when switching on on
approx. 29µs when switching off
Diagnosis
For 8 outputs each on diagnostic bit is 2. at the disposal, altogether
Are monitored:
- undervoltage
- wire break
- short-circuit against 0 and 24v
- over-temperature