2 - 20
CHASSIS
Edition 06.2005
2.8
Coupling module KOP (continued)
KOP power unit
Input values
Input voltage
UI
24V= admissible range of 22V to 35V
Three-phase bridge connection
max. ripple 3V
ss
max. rise time from 0V to 24V: 60ms
Input current
II
1.5A for UI 24V=
and a load of 4A for 5V, of 0.2A for
±
15V
Output values
Output voltage
UO
+5
+ 5V
Output current
IO
+5
4A for convective aeration
permanently short circuit proof
Output voltage
UO
+15
+ 15V
Output current
IO
+15
0.2A
permanently short circuit proof
Output voltage
UO
-15
- 15V
Output current
IO
-15
0.2A
permanently short circuit proof
The total load for + 5V and
±
15V must not exceed 25W. The load for each individual configuration
of devices can be ascertained resp. verified with the tables ‘Current consumption of the modules’
on the pages 3-11 and 3-12.