Faults
|
93
6 720 643 068 (2011/06)
Copyright (optional information)
F7
Flame detected even when burner is off.
B
Check electrodes; replace if defective.
B
Check flue gas system; clean or repair if defective.
B
Check PCB for moisture; dry if needed.
FA
After switching gas off: Flame is detected.
B
Check gas cock; replace if defective.
B
Clean condensate trap.
B
Check electrodes and leads; replace if defective.
B
Check flue gas system; clean or repair if needed.
Fd
Reset button pressed by mistake.
B
Press reset button again.
B
Check cable harness to safety high limit and gas cock for
ground connection.
Temperature gradient limiter: Temperature
rise too fast
B
Fully open service shut-off valves.
B
Check electrical connection between heating zone pump and
Heatronic.
B
Check pump plug connection per installation instructions.
B
Manually test operation of heating zone pump and replace if
defective.
B
Set pump speed correctly to match maximum output.
Display
Description
Elimination
Tab. 37 Faults shown on the display