Information about the appliance
|
27
6 720 643 068 (2011/06)
Copyright (optional information)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output
gps
18.0/4.5
17.5/5.6
Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input
°F ( °C)
171/135 (77/57)
171/135 (77/57)
Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input
°F ( °C)
133/91 (56/33)
133/91 (56/33)
CO
2
at max. nominal output
%
9.4
11.0
CO
2
at minimum nominal output
%
8.6
10.4
Condensate
Max. condensate quantity (t
R
= 86 °F (30 °C))
gph (l/h)
0.9 (3.5)
0.9 (3.5)
pH level, approx.
4.8
4.8
General
Voltage
VAC
120
120
Frequency
Hz
60
60
Max. power consumption (central heating mode)
W
205
205
Max. power consumption (Stand-by)
W
< 6
< 6
Noise level
dB(A)
≤
45
≤
45
Maximum supply temperature
°F ( °C)
194 (90)
194 (90)
Max. permissible operating pressure (P
MS
) heating
psi (bar)
30 (2.07)
30 (2.07)
Permissible ambient temperature
°F ( °C)
32 - 122 (0 - 50)
32 - 122 (0 - 50)
Nominal water capacity (heating)
Gal (L)
0.925 (3.5)
0.925 (3.5)
Weight (without packaging)
lbs. (kg)
103.6 (47)
103.6 (47)
Dimensions, W x H x D
inch
(mm)
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
Unit
NG
LPG (propane)
Tab. 7 Technical data heating boiler ZBR42-3A...