Heatronic boiler control settings
Copyright (optional information)
6 720 643 068 (2011/06)
Service function 2.A: Heating circuit pump lockout time
(only heating boiler ZBR..-3A)
During the runtime of an external 3-way valve actuator, the
space heating pump is blocked. Select the run time of the
3-way valve actuator between
01
-
24
(10 - 240) seconds
according to the manufacturer's documentation
.
Default setting
is
24
(240 seconds).
Service function 2.b: Maximum supply temperature
The values of this service function displayed depend on
the setting of the service function
0.E
:
Service function
0.E
is set to
00
(metric units):
•
The maximum supply temperature can be adjusted
between
35
and
88
(35 - 88 °C).
Service function
0.E
is set to
01
(US customary units):
•
The maximum supply temperature can be adjusted
between
96
and
190
(96 - 190 °F).
Default setting
is
190
(190 °F (88 °C)).
Service function 2.C: Purging function
The following settings are possible:
•
00
: Purging function off
•
01
: Purging function is switched on and after
completion automatically reset to
00
•
02
: Purging function is permanently on and is not reset
to
00
Default setting
is
00
for heating boilers ZBR..-3A
appliances, otherwise
01
.
Service function 2.d: Thermal disinfection (legionella
protection)
When this service function is enabled, the DHW is
permanently
heated to approx. 158 °F (70 °C) if the DHW
temperature dial has been turned clockwise to
max
.
The following settings are possible:
•
00
: Thermal disinfection not enabled
•
01
: Thermal disinfection enabled
Default setting
is
00
(disabled).
Service function 2.F: Operating mode
With this service function, you can temporarily change the
appliance's operating mode.
The following settings are possible:
•
00
: Default mode; the appliance runs according to
control settings.
•
01
: The appliance runs for 15 minutes at minimum
output. The display shows 2.F. When this service
function is aborted or has been active for 15 minutes,
the appliance reverts to default mode.
•
02
: The appliance runs for 15 minutes at maximum
output. The display shows 2.F. When this service
function is aborted or has been active for 15 minutes,
the appliance reverts to default mode.
Default setting
is
00
.
NOTICE:
System damage or boiler
malfunction!
B
Never change the setting of this service
function on combi boiler ZWB..-3A
appliances.
This setting is only active if Service function
1. F: Pump mode is set to 01 (3-way valve).
When the appliance is switched ON for the
first time, it performs a once-only purging
sequence. This involves the heating zone
pump switching on and off at intervals (for
approx. 4 minutes).
The display shows
in alternation with the
supply temperature.
This service function allows activating the
purging function manually, e.g. after servicing.
WARNING:
Risk of scalding!
Hot water can result in severe scalding.
B
Carry out thermal disinfection only outside
the normal hours of use.
B
Install a tempering valve if this function is
enabled permanently.