16.3 Faults that are not shown on the display
Appliance faults
Elimination
Combustion noise too loud; rumbling noises
B
Insert code plug correctly; replace if defective.
B
Check gas type.
B
Check inlet gas pressure; adjust if defective.
B
Check flue gas system; clean or repair if defective.
B
Check gas/air ratio in the combustion air and flue gas; replace gas valve if
defective.
Flow noises
B
Set pump speed correctly to match maximum output.
B
Set pump mode.
Heating-up takes too long
B
Set pump speed correctly to match maximum output.
B
Set pump mode.
Flue gas readings incorrect; CO levels too high
B
Check gas type.
B
Check inlet gas pressure; adjust if defective.
B
Check flue gas system; clean or repair if defective.
B
Check gas/air ratio in flue gas; replace gas valve if defective.
Violent ignition, poor ignition
B
Check gas type.
B
Check inlet gas pressure; adjust if defective.
B
Check power supply.
B
Check electrodes for visual damage; replace if defective.
B
Check flue gas system; clean or repair if defective.
B
Check gas/air ratio; replace gas valve if defective.
B
Check gas valve; replace if defective.
B
Check burner; replace if required.
DHW has unpleasant odor or has a dark color
B
Perform thermal disinfection of the DHW circuit.
B
Replace sacrificial anode in the tank (if installed).
B
Consult local water department.
Set supply temperature (e.g. of the FW200 control)
exceeded
B
Switch off automatic anti-cycle timer, i.e., set value to 0.
B
Set the required anti-cycle timer, e.g. default setting of 3 minutes.
Condensate in air box
B
Insert diaphragm in the mixer unit per installation instructions; replace if
defective.
DHW temperature is not reached (combi boiler
ZWB..-3A only)
B
Insert code plug correctly; replace if defective.
B
Check whether voltage (120 VAC) is present between terminal 1 and termi-
nal 3; repair if defective.
B
Check turbine; replace if defective.
Heatronic is flashing (i.e. all buttons, all display seg-
ments, burner indicator etc. are flashing)
B
Replace fuse Si 3 (24 V) (6.3 A fuse according to IEC default).
Tab. 38 Faults not shown on the display