60
|
Commissioning
Copyright (optional information)
6 720 643 068 (2011/06)
7.3
Setting up space heating
Set the maximum supply temperature based on the
structure's heat loss on design day.
B
In order to set the maximum supply temperature, turn
the boiler high limit dial
.
Fig. 55 Switch on heat
If the burner is operating, the burner operation
indicator lamp is illuminated.
7.4
Programming the FW 200 heating
control unit
Fig. 56 FW 200 heating control
7.5
After commissioning
B
Check flue path for tightness.
B
Check gas supply dynamic pressure (
Æ
page 78).
B
Check that condensate is being discharged from the
condensate hose. If that is not the case, switch the
appliance first OFF and then ON again using the ON/
OFF switch. That activates the trap filling sequence
(
Æ
page 70). Repeat the procedure several times until
condensate starts running out.
B
Complete commissioning report (
Æ
page 97).
Boiler high
limit dial
Typical supply
temperatures
Sample application
1
approx. 95 °F
(35 °C)
Frost protection
2
approx. 109 °F
(43 °C)
3
approx. 122 °F
(50 °C)
Radiant floor heating
system
4
approx. 140 °F
(60 °C)
Panel radiator system
5
approx. 153 °F
(67 °C)
Cast iron radiator
system
6
approx. 167 °F
(75 °C)
max
approx. 194 °F
(90 °C)
Baseboard and
convector system
Tab. 24 Typical supply temperatures
With radiant floor heating, limit the maximum
permissible supply temperature as
recommended by the manufacturer.
eco
reset
6 720 641 933-53.1O
max
1
2
3
4
5
6
max
1
2
3
4
e
6
min
Observe the operating instructions for the
heating control included in the scope of
delivery. There you can read:
B
How to set the operating mode and the
heating curve for outdoor reset controls
B
How to adjust the room temperature
B
How to heat economically and comfortably
B
How the control can be mounted in the
boiler or in the living space
9
12
h
15
18
21
24
h
3
6
6 720 612 660-07.2O