84
|
Inspection and maintenance
Copyright (optional information)
6 720 643 068 (2011/06)
14.1.5 Burner servicing
B
Remove burner lid (steps 1 - 4).
Fig. 84 Removing the burner cover
B
Remove burner and clean its components.
Fig. 85 Burner
B
Reinstall burner in reverse order, including a new gasket
if necessary.
B
Adjust the gas-air ratio (
Æ
page 76).
14.1.6 Heat exchanger block inspection and cleaning
B
Remove the inspection cover (
Æ
page 12) and any
sheet metal insert below, if installed.
B
Determine degree of soiling of the heat exchanger
through visual inspection.
If mechanical cleaning is required:
For cleaning the heat exchanger, Bosch offers the service
accessory kit which includes main heat exchanger gaskets,
the heat exchanger brush and heat exchanger cleaning
blade (part-# 7719001998).
B
Remove the condensate trap (steps 1 and 2) and place
a suitable container underneath.
Fig. 86 Removing the condensate trap
DANGER:
Fire danger!
B
Only operate the burner while installed in a
boiler.
1
2
4
6 720 641 933-95.1o
3
7 181 465 330-08.2R
NOTICE:
Damage to the coating of the heat
exchanger.
B
Cleaning of the heat exchanger should not
be necessary until five years after the initial
commissioning.
B
Only use a Bosch cleaning blade and Bosch
cleaning brush (
Æ
page 114).
B
Only clean heat exchanger in case if soiling
is clearly visible.
6 720 641 933-93.1o
1
2