Heatronic boiler control settings
|
71
6 720 643 068 (2011/06)
Copyright (optional information)
Service function 5.b: Fan post purge time
This service function allows setting the time the fan purges
after the burner is shut off.
The post purge time can be set from
01
to
18
(10 - 180
seconds).
Default setting
is
03
(30 seconds).
Service function 5.E: Functionality of black plug in boiler
junction box
With this service function you can set the functionality of
the black plug in the boiler junction box (
Æ
page 56).
The following settings are possible:
•
00
: Off - black connector in junction box is disabled
(120VAC output deactivated).
•
01
: DHW recirculation pump enabled - see FW200
instructions on how to set a recirculation pump
program.
•
02
: External heating zone pump in heating circuit
without 3-way valve controlled by FW 200.
•
03
: External heating zone pump in heating circuit
without mixer controlled by Heatronic running in
parallel with boiler pump in central heating mode
Default setting
is
03
.
Service function 5.F: Set inspection interval
This service function allows setting the number of months
after which the 'service due' reminder
appears
on the
display
alternating with the supply temperature.
The number of months can be set from
00
-
72
(0 to 72 months).
Default setting
is
00
(disabled).
Service function 6.A: Display the latest fault code
Use this service function to display the most recent fault
code.
Service function 6.b: Room temperature control, current
voltage, terminal 2
The current voltage of the analog control at terminal 2 is
displayed.
Possible displays are:
•
00
-
24
: 0 V to 24 V in increments of 1 V
Service function 6.C: Supply temperature required by
outdoor reset control
This service function allows displaying the current target
supply temperature set by the outdoor reset control.
Service function 6.d: Current DHW turbine flow rate
(only combi boiler ZWB..-3A)
The current flow rate of the DHW turbine is displayed.
Service function
0.E
is set to
00
(metric units):
•
0.0.
-
99.9.
: 0.0 to 99 l/min in increments of 0.1 l/min
Service function
0.E
is set to
01
(US-customary units):
•
0.0.
-
99.9.
: 0.0 to 99 gpm in increments of 0.1 gpm
Service function 7.A: Indicator lamp for burner operation
/ faults
With this service function you can activate and deactivate
the indicator lamp for burner operation (continuously
illuminated) and faults (flashing).
The following settings are possible:
•
00
: Off
•
01
: On (burner operation) and flashing (fault present)
Default setting
is
00
.
If
U0
appears on the display, the function was
already set via the FW200 control.
NOTICE:
System damage or boiler
malfunction!
B
Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.