76
|
Gas type conversion
Copyright (optional information)
6 720 643 068 (2011/06)
11.2 Installation location higher than
2,000 feet (610 m) above sea level
Input and output rates are reduced at higher altitudes due
to thin air with reduced oxygen levels.
ZBR42-3A... and ZWB42-3A... appliances are derated at
3 % per 1000 feet (305 m).
ZBR16-3A..., ZBR28-3A..., ZBR35-3A... and ZWB28-3A...
appliances offer altitude adjustment which compensates
for the effects of thin air, and are therefore NOT derated
up to 6000 feet (1829 m). Above 6000 feet (1829 m) a
rate of 3 % per 1000 feet (305 m) applies.
B
Correction of the fan speed curve of the burner:
Use service function 0.d to adjust the elevation setting
(
Æ
page 72).
11.3 Setting the gas-air ratio (CO
2
or O
2
)
B
Switch the appliance OFF using the ON/OFF switch.
B
Remove the cover (
Æ
page 41).
B
Switch the appliance ON using the ON/OFF switch.
B
Open one of the flue gas test ports.
Fig. 69 Open one of the flue gas test ports
B
Insert the probe approx. 2-3/4 inches (70 mm) into the
test port and seal around it.
B
Press and hold the emissions test button until it
lights up.
The display shows the supply temperature alternating
with
=
maximum set output in heating mode
.
B
Briefly press the emissions test button .
The display shows the supply temperature in
alternation with
=
maximum nominal output
.
B
Measure the CO
2
or O
2
level and the CO content of the
flue gas (
Æ
Section 12).
The Bosch Greenstar boiler is factory set for
installation below 2000 feet (610 m) above
sea level.
6 720 641 933-79.1O