74
|
Heatronic boiler control settings
Copyright (optional information)
6 720 643 068 (2011/06)
Service function 9.d: Set fan start speed
At higher elevations the boiler fan may need to spin faster
upon startup to ensure reliable ignition every time. The
start speed of the boiler fan can be set from
45
to
77
revolutions per second (1/s).
Default setting
is
50
.
Service function 9.E: Turbine signal delay
(only combi boiler ZWB..-3A)
This service function allows setting a time delay to prevent
the appliance starting up as a result of transient pressure
spikes in the water supply.
Through spontaneous pressure change in the water
supply, the flow meter (turbine) can signal that DHW is
being drawn and cause the burner to come on
unnecessarily.
The turbine signal delay can be set from
02
to
08
(0.5
seconds to 2 seconds) in increments of 0.25 seconds.
Default setting
is
04
(1 second).
Service function 9.F: Heating zone pump post purge
This service function allows setting a pump post purge
time after the end of the heat demand from the external
control.
The pump post purge time can be set from
01
to
10
(1 to 10 minutes).
Default setting
is
03
.
Service function A.b: Display DHW temperature
This service function allows displaying the current DHW
temperature.
Service function A.C: Display DHW tank temperature
This service function allows displaying the temperature of
the DHW tank temperature sensor.
Service function b.F: Solar DHW backup heating delay
(only combi boiler ZWB..-3A)
For systems with a solar thermal DHW tank in series before
the DHW line of the combi boiler. DHW heating by the
boiler will be suppressed expecting that solar thermal
DHW will reach the hot water temperature sensor prior
eliminating the need to run the boiler. Set the heating
delay in accordance with system conditions.
The start delay can be set between 00 to 50 (0 to 50
seconds) in increments of 1 second.
Default setting
is
00
.
Service function C.d: Display current heat demand
Available displays are:
•
00
: No heat demand
•
01
: Space heating demand present
•
02
: DHW heat demand present
NOTICE:
System damage or boiler
malfunction!
B
Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.
If this setting is enabled, the DHW demand
signal is no longer available
Æ
page 61.