UPH pan/tilt devices require no particular maintenance.
10.1
Cleaning
To clean the device, use neutral detergent and a non-abrasive cloth.
10.2
Replacing the Fuses
There are two (2) preset fuses on the connection board. Sizes are related to the power supply
voltage, as shown in the table below.
Figure 10.1
Fuses on the Connection Board
Standard Models: Fuse Values for Replacement (Reference #1)
Refer to
Figure 10.1
, Item 1, above for fuse locations.
IR Modes: Fuse Values for Replacement (Reference #2)
Refer to
Figure 10.1
, Item 2, above for fuse locations.
Voltage
Fuse F1
Fuse F2
24 VAC 50/60 Hz
T 4A L 250 V
T 6.3A H 250 V
120 VAC 50/60 Hz
T 4A L 250 V
T 4A H 250 V
230 VAC 50/60 Hz
T 4A L 250 V
T 2A H 250 V
Voltage
Fuse F1
Fuse F2
24 VAC 50/60 Hz
T 4A L 250 V
T 8A H 250 V