6-4
Electrical Data
Rexroth IndraDrive C HCS03.1
DOK-INDRV*-HCS03.1****-PR02-EN-P
WARNING
Damage due to drive controller overload!
⇒
Make sure the specified performance data - peak
power and continuous power - are complied with by
correct drive dimensioning and selective fusing in the
mains connection.
Mains Connection Power and DC Bus Continuous Power
The diagrams below illustrate the interrelation between mains connection
power (S
LN
) and DC bus continuous power (P
DCcont
) with and without the
use of mains chokes.
S
LN
depending on P
DC cont
for HCS03.1-E-W0070 @3AC400V/4kHz
0,00
10,00
20,00
30,00
40,00
50,00
2,5
5
7,5
10
12,5
15
17,5
20
22,5
25
27,5
30
P
DC cont
[kW]
S
LN
[kVA]
with mains choke
without mains choke
Fig. 6-4:
Interrelation of S
LN
/ P
DC
for HCS03.1-E-W0070
S
LN
depending on P
DC cont
for HCS03.1-E-W0100 @3AC400V/4kHz
0,00
10,00
20,00
30,00
40,00
50,00
60,00
70,00
0
10
20
30
40
50
P
DC cont
[kW]
S
LN
[k
V
A
]
with mains choke
without mains choke
Fig. 6-5:
Interrelation of S
LN
/ P
DC
for HCS03.1-E-W0100
Summary of Contents for Rexroth IndraDrive C HCS03.1
Page 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 85: ......