Rexroth IndraDrive C HCS03.1
Electrical Data
6-1
DOK-INDRV*-HCS03.1****-PR02-EN-P
6 Electrical
Data
Note:
The current and power data below apply when the allowed
motor cable length is complied with (see data in section "X5,
Motor Connection"). They refer to 3AC400 V.
6.1
Power Section - Mains Supply
Designation
Symbol
Unit
HCS03.1E-
W0070
HCS03.1E-
W0100
HCS03.1E-
W0150
HCS03.1E-
W0210
three-phase mains
connection
allowed
single-phase mains
connection
not allowed
rotary field
no rotary field condition
total power factor TPF at
P
DC
with / without mains
choke
cos
φ
=1/
λ
L
0,85/0,57
0,83/0,59
0,81/0,61
0,78/0,62
power factor of
fundamental component
DPF P
DC
with / without
mains choke
cos
φ
h1
0,95/0,64
0,95/0,67
0,94/0,70
0,93/0,73
assigned mains choke
HNL01.1E-
0571-N0050-A-
500-NNNN
0362-N0080-A-
500-NNNN
0240-N0106-A-
500-NNNN
0170-N0146-A-
500-NNNN
mains input voltage range
U
LN
V
3AC400 ... 500 +10% -15%
mains frequency
f
LN
Hz
50 ... 60 ± 2 Hz
mains input continuous
current at P
DC cont
I
L,cont
A
50
80
106
146
maximum inrush current
(at max. input voltage)
I
L, trans max
(on)
A
2,8
5,7
5,7
17
mains connection power
at P
DC_cont
;
U
LN
=AC400V; with
HNL01.1E
S
LN
kVA
35
55,2
72,9
99,3
mains connection power
at P
DC_cont
;
U
LN
=AC400V; without
HNL01.1E
S
LN
kVA
22,6
40,3
54
76
Fig. 6-1:
Electrical data: power section - mains supply
Summary of Contents for Rexroth IndraDrive C HCS03.1
Page 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 85: ......