6-8
Electrical Data
Rexroth IndraDrive C HCS03.1
DOK-INDRV*-HCS03.1****-PR02-EN-P
6.6
Power Section - Examples of Allowed Output Current
Profiles
The capacity of the drive controllers when operated with mains choke is
described below with examples of load profiles.
Designation
Symbol
Unit
HCS03.1E-
W0070
HCS03.1E-
W0100
HCS03.1E-
W0150
HCS03.1E-
W0210
output current profile
for overload
operation
overload capacity:
Iout_base
Iout_peak
K =
T
I
out_base
t
I
I
out_peak
t
maximum output
current
t=400ms; T=4s
I
out_peak1 (4 kHz)
I
out_peak1 (8 kHz)
I
out_peak1 (12 kHz)
I
out_peak1 (16 kHz)
A
70
50
36
28
100
70
50
40
150
100
75
60
210
150
100
75
base load current
available at
maximum current
t=400ms; T=4s
I
out_base1 (4 kHz)
I
out_base1 (8 kHz)
I
out_base1 (12 kHz)
I
out_base1 (16 kHz)
A
35
25
18
14
54
37
28
19
67
50
36
26
116
78
59
45
maximum output
current
t=2s; T=20s
I
out_peak3 (4 kHz)
I
out_peak3 (8 kHz)
I
out_peak3 (12 kHz)
I
out_peak3 (16 kHz)
A
63
45
32
23
90
65
45
32
147
100
70
50
210
150
100
80
base load current
available at
maximum current
t=2s; T=20s
I
out_base3 (4 kHz)
I
out_base3 (8 kHz)
I
out_base3 (12 kHz)
I
out_base3 (16 kHz)
A
35
25
19
15
49
30
25
21
59
44
35
28
109
73
57
41
Summary of Contents for Rexroth IndraDrive C HCS03.1
Page 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 85: ......