Rexroth IndraDrive C HCS03.1
Electrical Data
6-17
DOK-INDRV*-HCS03.1****-PR02-EN-P
CAUTION
Damage caused by voltage arcing!
⇒
When electrical lines and not the contact bars are
used to connect the converter, the connections must
be executed correctly.
CAUTION
Damage caused by voltage arcing!
⇒
If drive controllers are stacked in the control cabinet,
the connections for the DC buses between the drive
controllers have to be correctly made.
CAUTION
Damage due to converter overload!
⇒
Only converters of identical DC bus power may be
connected.
X1, Module Bus
The module bus is used to exchange data between two converters of
identical rating or between one converter and inverters connected to the
DC bus.
X1f2.FH7
X1 out
X1 in
Fig. 6-20:
Graphic representation module bus
Type
No. of poles
Type of design
Ribbon cable connector
8
Connector at device
Ribbon cable socket
8
Socket at ribbon cable
Fig. 6-21:
Design module bus
Note:
When extension cables are used for the module bus, they
must be shielded. Their total length must not exceed 40 m.
Graphic Representation
Design
Summary of Contents for Rexroth IndraDrive C HCS03.1
Page 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 85: ......