AMAX panel 2000 / AMAX panel 2000 EN
System Informations 2 | en
63
Bosch Sicherheitssysteme GmbH
Installation Manual
F.01U.241.127 | V4 | 2011.12
3. 3 Times Alarm Lockout
Same as 1 time alarm lockout, but the lock out time is 3.
4. 4- 6 Times Alarm Lockout
Same as 3 times alarm lockout, but the lock out time is 6.
5. Alarm Timer Lockout
Repeat the process of alarm lockout, but no lockout time limits.
8.1.8
Zone Tamper
The system will support the detector tamper of the zone. This will make sure the zone really
works in normal status. The process is below:
1.
If we use the 24-Hour tamper, we can only use the NC contact point. Refer to zone EOL
section, when the zone is programmed to support the 24-Hour zone, it will use the 24-
Hour tamper wiring. If the zone detected the 24-Hour tamper triggered, the zone will be
processed as 24-Hour zone. If the zone detected as zone alarm, it will be processed as
the programmed type.
2.
Refer to zone EOL section, when the zone is programmed to disable the 24-Hour tamper
zone, it will use the single EOL wiring.
3.
If the zone detected the zone alarm triggered, it will be processed as the programmed
type.
8.1.9
Zone Fault
This fault operates when the zone fails. The fault is reset when the zone is restored.
The zone fault occurs on any below condition:
1.
24-hour and instant zone, if force-arm enabled and not ready at arm operation, generate
a zone trouble event.
2.
When the zone is locked out.
3.
Delay and follower zone, if force-arm enabled and not ready at exit delay timer expired,
generate a zone trouble event.
4.
24-hour zone, if it is not ready at un-bypass time, generate a zone trouble event.
Fault Restore:
1.
The zone is normal.
2.
Instant, follower, and delay zones when performing the disarm, the system will generate
a zone trouble restore if it is still in trouble state.
8.1.10
Zone Report
The control panel will report the zone status. For detailed information refer to
Section 7.7.3 Report Transmission Sequence, page 53.
8.1.11
Zone Chime Mode
The system will support the chime mode.
The process is as follows:
1.
If the chime mode is used and a zone is triggered then the keypad buzzer will sound for 1
second (only in disarmed status).
8.2
System Reporting Information
This section covers features that are involved with basic housekeeping of the system. These
include monitoring of the zones if they are isolated from the system, or more importantly, they
are actually operating, the status of both the AC MAINS and DC power to the system, and
keypad-generated alarms activated by the user.