Orion ISS
www.bolid.com
88
−
1 ÷ 5s in the Relay Activation Time fields (the time sufficient for the strike to be actuated)
−
‘Switch off after door being opened’ flag (for the strike to be cocked properly upon quick
passing)
Please note that Free Pass Access mode can not be implemented for an access point if the
electric strike is used as a locking unit.
If magnet locks are in use as the locking units, set at the Outputs tab
−
‘Switch Off for a Time’ in Executive Program field for both the relays
−
5 ÷ 20s in the Relay Activation Time fields (maximum passage time)
−
‘Switch off after door being opened’ or ‘Switch off after door being closed’ flag (for the lock
to be secured just after a passage detection)
Other configuration parameters are adjusted depending on specific user needs and desires.