S2000-2 S2000-2
Programming
73
www.bolid.com
−
For Two Entrance Doors, One Entrance/Exit Door and Turnstile
modes, after granting the ac-
cess the controller is waiting for a passage to be detected (the door to be open, the turnstile to
be rotated and so on) for the Relay Activation Time, but at least for 10 seconds. Before sensing
the passage or this time having been expired the controller ignores all attempts to present iden-
tifiers to the reader again
−
When the sensor has just actuated the PASSAGE message is generated by the controller
−
Monitoring the door for held or force open has been available (see the description of the
Forced
Open
Monitoring
and
Held Open Monitoring
parameters)
−
The relay which controls the lock can be switched off lock before the
Relay Control Time
hav-
ing been expired (see the description of the
Switch Off After Door Being Opened
and
Switch
Off After Door Being Closed
parameters)
If the
Passage Sensor
parameter is unset, the mentioned above functions are unavailable, passing is
not expected and in the Two Entrance Doors, One Entrance/Exit Door and Turnstile modes the sys-
tem indicates the fact of access granting by means of the reader LED, which is switched on for the
Relay Activation Time
,
but at least for 2 seconds.
If the
Forced Open Monitoring
parameter is set, door opening preceded by no access granting will
cause the DOOR FORCED alarm message to be generated and the light and sound alarms to be
activated.
If the
Held Open Monitoring
parameter is set, door being opened for more than
Held Open Timeout
will cause the DOOR LEFT OPEN alarm message to be generated and the light and sound alarms to
be activated.
The
LED Control Polarity
parameter defines the active logic level to control red and green LEDs of
the reader. If the
Forward
control polarity is set, the high logic level is used to activate the LEDG and
LEDR of the controller. If the
Reverse
polarity is selected, the LEDs will be activated by low logic
level.
It is advisable to set this parameter to
¾
Forward
(1 active) for IButton readers and for most readers with Wiegand interface,
¾
Backward
(0 active) for most readers with Touch Memory interface (except iButton readers)
The
Sounder Control Polarity
parameter defines the active logic level to control the sounder of the
reader similarly to those of the LED Control Polarity.
It is advisable to set this parameter to
¾
Forward
(1 active) for most readers with Wiegand interface,
¾
Backward
(0 active) for most readers with Touch Memory interface
Summary of Contents for S2000-2
Page 1: ...Orion ISS Access Controller S2000 2 User s Manual ISO 9001 ...
Page 5: ...S2000 2 Features and Design 5 www bolid com FEATURES AND DESIGN ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...S2000 2 Specifications 9 www bolid com SPECIFICATIONS ...
Page 12: ...Orion ISS www bolid com 12 ...
Page 13: ...S2000 2 Operating 13 www bolid com OPERATING ...
Page 47: ...S2000 2 Installation 47 www bolid com INSTALLATION ...
Page 67: ...S2000 2 S2000 2 Programming 67 www bolid com S2000 2 PROGRAMMING ...
Page 89: ...S2000 2 Maintenance 89 www bolid com MAINTENANCE ...
Page 94: ...Orion ISS www bolid com 94 ...
Page 95: ...S2000 2 95 www bolid com Appendix Connecting Some Models of Readers to the S2000 2 Controller ...