S2000-2 S2000-2
Programming
79
www.bolid.com
If the
Confirmation Only
entry (exit) mode is selected for the all keys included in the access group
such the keys are used only to confirm access rights for keys of another access groups and cannot be
used to gain access by itself.
If the
Two-person
or
Three-person Rule
passage mode (see Passage Modes and Two or More Per-
son Rule Access Control Section of this Manual) is selected for an access group, then to gain access
owners of the keys of this access group must present their keys followed by presenting one more key
(two keys) assigned with the other access group (groups). The numbers of these groups are specified
by values of
First Access Group to Confirm Entry (Exit)
and
Second Access Group to Confirm
Entry (Exit)
parameters. If for example the Two-person Rule is selected as entry mode the controller
after successful identification of the key of programmed access group will be waiting for presenting a
key assigned with the access group specified by
First Access Group to Confirm Entry
. If otherwise
the Three-person Rule is selected, the controller first verifies the access rights of the key of the pro-
grammed access group, then verifies that the next presented key has the group number specified by
First Access Group to Confirm Entry
, and finally requires the presenting of a third key included in
Second Access Group to Confirm Entry
. The exit modes are implemented similarly.
If the
Arming/Disarming
parameter is set the keys contained in this access group can be used to
arm and disarm alarm loops of the S2000-2 controller. The
Arm Loop 1
,
Arm Loop 2
,
Disarm Loop
1
,
Disarm Loop 2
parameters defines specific actions which are permitted for owners of keys in-
cluded in the access group.
The
Time Schedule
for arming/disarming represents a number of time schedule defining intervals of
time when arming/disarming alarm loops is permitted for the keys. If this parameter is equal to 0, arm-
ing/disarming is enabled at any time. Parameters of all other available 16 time schedules are pro-
grammable (see Time Schedules Section of this Manual).
If the both attributes
Access
and
Arming/Disarming
are set on for the keys included in the access
group these keys are called
combined
(that is, multifunctional). The combined keys can be used for:
−
Access and loop arming/disarming (if the keys are assigned with the
User
type)
−
Unlocking/restoring Controlled Access mode and loop arming/disarming (if the keys are as-
signed with the
Unlocking
type)
−
Locking/restoring Controlled Access mode and loop arming/disarming (if the keys are assigned
with the
Locking
type)
In order to control the loop arming/disarming by a combined key the controller has to be preliminary
switched to Ready to Arm/Disarm mode or the key has to be held near the reader within the specified
time (see Alarm Loops Section of this Manual).
Summary of Contents for S2000-2
Page 1: ...Orion ISS Access Controller S2000 2 User s Manual ISO 9001 ...
Page 5: ...S2000 2 Features and Design 5 www bolid com FEATURES AND DESIGN ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...S2000 2 Specifications 9 www bolid com SPECIFICATIONS ...
Page 12: ...Orion ISS www bolid com 12 ...
Page 13: ...S2000 2 Operating 13 www bolid com OPERATING ...
Page 47: ...S2000 2 Installation 47 www bolid com INSTALLATION ...
Page 67: ...S2000 2 S2000 2 Programming 67 www bolid com S2000 2 PROGRAMMING ...
Page 89: ...S2000 2 Maintenance 89 www bolid com MAINTENANCE ...
Page 94: ...Orion ISS www bolid com 94 ...
Page 95: ...S2000 2 95 www bolid com Appendix Connecting Some Models of Readers to the S2000 2 Controller ...