ACCESS MODES
In all the controller’s operation modes (
Two Entrance Doors
,
One Entrance/Exit Door
,
Turnstile
,
Swing-beam Barrier
, and
Two Sluice Doors
) each of the two readers connected to the controller can
operate in one of three following access modes:
−
Controlled Access Mode
−
Access Locked Mode
−
Free Pass Mode
If the access is locked (the Access Locked mode) an access can be granted only by the EXIT button
or by a remote network controller command.
In the Free Pass mode a door (turnstile, swing-beam barrier) is permanently open for free passing
(without identification and passage detection).
In the Free Pass or Access Locked modes the S2000-2 controller takes into account only special keys
(
Unlocking, Locking
or
Master
), as well as keys intended for loop and partition arming/disarming. Pre-
senting an
Unlocking
or
Locking
key restores the Controlled access mode – see Controlled Access
Mode Section below. Presenting a
Master
key to a reader switches the S2000-2 to the key program-
ming mode (local key programming
see Key Programming section of this Manual).
The access mode for one S2000-2 reader (access to one direction) can differ from the access mode
of another S2000-2 reader (access to another direction).
Access Locked Mode
Access can be locked for a reader by means of one of the following ways:
−
by a Locking key presenting to the reader (with the key time schedule and validity being
checked)
−
by the relevant command of the network controller, received via the RS-485 interface
−
by arming of an access locking alarm loop
Access Locked by a Locking Key or Network Controller Command
If access is locked by a
Locking
key or the remote network controller command, the LED of the rele-
vant reader begins flashing with red color (one flash per second with short pauses), the sounders of
the controller and the relevant reader, if enabled, playing four beeps.
In such a case an access is locked for all the keys stored in the controller memory (that is, local ac-
cess is locked). Only centralized access or access by pressing the EXIT button (if exists) is possible.
(Centralized access can be denied only by the network controller tools).
Summary of Contents for S2000-2
Page 1: ...Orion ISS Access Controller S2000 2 User s Manual ISO 9001 ...
Page 5: ...S2000 2 Features and Design 5 www bolid com FEATURES AND DESIGN ...
Page 8: ...Orion ISS www bolid com 8 ...
Page 9: ...S2000 2 Specifications 9 www bolid com SPECIFICATIONS ...
Page 12: ...Orion ISS www bolid com 12 ...
Page 13: ...S2000 2 Operating 13 www bolid com OPERATING ...
Page 47: ...S2000 2 Installation 47 www bolid com INSTALLATION ...
Page 67: ...S2000 2 S2000 2 Programming 67 www bolid com S2000 2 PROGRAMMING ...
Page 89: ...S2000 2 Maintenance 89 www bolid com MAINTENANCE ...
Page 94: ...Orion ISS www bolid com 94 ...
Page 95: ...S2000 2 95 www bolid com Appendix Connecting Some Models of Readers to the S2000 2 Controller ...