96
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code
Name/Description
Adjustment range
Factory setting
LO3-
•
[LO3 CONFIGURATION]
Can be accessed if an ER40 option card "In-/Out extension" has been inserted
LO3
• [LO3 assignment]
[No]
(nO)
Identical to LO1 (see page
95
).
LO3d
• [LO3 delay time]
0 to 9,999 ms
0
The delay cannot be set for the
[No drive flt]
(FLt)
,
[Output cont]
(OCC)
,
[DC charging]
(dCO)
,
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
LO3S
POS
nEG
• [LO3 active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
The
[1]
(POS)
configuration cannot be modified for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC),
assignments.
LO3H
• [LO3 holding time]
0 to 9,999 ms
0
The holding time cannot be set for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.
LO4-
•
[LO4 CONFIGURATION]
Can be accessed if an ER40 option card "In-/Out extension" has been inserted
LO4
• [LO4 assignment]
[No]
(nO)
Identical to LO1 (see page
95
).
LO4d
• [LO4 delay time]
0 to 9,999 ms
0
The delay cannot be set for the
[No drive flt]
(FLt)
,
[Output cont]
(OCC)
,
[DC charging]
(dCO)
,
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes true.
LO4S
POS
nEG
• [LO4 active at]
[1]
(POS)
Configuration of the operating logic:
-
[1]
: State 1 when the information is true
-
[0]
: State 0 when the information is true
The
[1]
(POS)
configuration cannot be modified for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC),
assignments.
LO4H
• [LO4 holding time]
0 to 9,999 ms
0
The holding time cannot be set for the
[No drive flt]
(FLt)
,
[DC charging]
(dCO)
and
[Input cont.]
(LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information
becomes false.