129
[1.7 APPLICATION FUNCT.]
(FUn-)
(1) The parameter can also be accessed in the
[1.3 SETTINGS]
(SEt-)
menu.
Code
Name/Description
Adjustment range
Factory setting
JOG-
•
[JOG]
Note: This function cannot be used with certain other functions. Follow the instructions on page
115
.
JOG
• [JOG]
[No]
(nO)
nO
LI1
-
-
C101
-
-
-
Cd00
-
Pulse operation.
The JOG function is only active if the command channel and the reference channels are on the
terminals.
Selecting the assigned logic input or bit activates the function.
-
[No]
(nO)
: Not assigned
-
[LI1]
(LI1)
to
[LI6]
(LI6)
-
[LI7]
(LI7)
to
[LI10]
(LI10)
: If VW3A3201 logic I/O card has been inserted
-
[LI11]
(LI11)
to
[LI14]
(LI14)
: If VW3A3202 extended I/O card has been inserted
-
[C101]
(C101)
to
[C115]
(C115)
: With integrated Modbus in [I/O profile] (IO) configuration
-
[C201]
(C201)
to
[C215]
(C215)
: With integrated CANopen in [I/O profile] (IO) configuration
-
[C301]
(C301)
to
[C315]
(C315)
: With a communication card in [I/O profile] (IO) configuration
-
[C401]
(C401)
to
[C415]
(C415)
: With a Controller Inside card in [I/O profile] (IO) configuration
-
[CD00]
(Cd00)
to
[CD13]
(Cd13)
: In [I/O profile] (IO) configuration can be switched with possible logic inputs
-
[CD14]
(Cd14)
to
[CD15]
(Cd15)
: In [I/O profile] (IO) configuration can be switched without logic inputs
The function is active when the assigned input or bit is at 1.
Example: 2-wire control operation (tCC = 2C)
JGF
• [Jog frequency]
(1)
0 to 10 Hz
10 Hz
The parameter can be accessed if
[JOG]
(JOG)
is not
[No]
(nO)
or if a function key has been assigned to
JOG (see page
113
).
Reference in jog operation
JGt
• [Jog delay]
(1)
0 to 2.0 s
0.5 s
The parameter can be accessed if
[JOG]
(JOG)
is not
[No]
(nO)
or if a function key has been assigned to
JOG (see page
113
).
Anti-repeat delay between 2 consecutive jog operations.
Parameter that can be modified during operation or when stopped.
1
0
1
0
1
0
0
Ramp
forced to 0.1 s
Reference
JGF reference
JGF reference
LI (JOG)
Forward
Reverse
Ramp
DEC/DE2
Motor
frequency
JGt