80
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Configuration of analog inputs and Pulse input
The minimum and maximum input values (in volts, mA, etc.) are converted to% in order to adapt the references to the application.
Minimum and maximum input values:
The minimum value corresponds to a reference of 0% and the maximum value to a reference of 100%. The minimum value may be greater
than the maximum value:
For +/- bidirectional inputs, the min. and max. are relative to the absolute value, for example, +/- 2 to 8 V.
Negative min. value of Pulse input:
Range (output values): For analog inputs only
This parameter is used to configure the reference range to [0%
V
100%] or [-100%
V
+100%] in order to obtain a bidirectional output from
a unidirectional input.
Reference
100%
0%
[Min value]
(CrLx or
ULx or PIL)
[Max value]
(CrHx or
UHx or PFr)
20 mA or
10 V or
30.00 kHz
Reference
100%
0%
[Min value]
(CrLx or
ULx or PIL)
[Max value]
(CrHx or
UHx or PFr)
Current or
voltage or
frequency
input
Current or
voltage or
frequency
input
20 mA or
10 V or
30.00 kHz
Reference
100%
0%
[RP min
value] (PIL)
[RP max value]
(PFr)
30.00
kHz
Frequency
input
-30.00
kHz
Reference
100%
0%
[Min value]
[Max value]
Range 0
V
100%
Reference
100%
0%
[Min value]
[Max value]
Current
or
voltage
input
Current
or
voltage
input
-100%
Range -100%
V
+100%
20 mA
or 10 V
20 mA
or 10 V