57
[1.3 SETTINGS]
(SEt-)
(1) In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
Code
Name/Description
Adjustment range
Factory setting
tLIM
• [Motoring torque lim]
0 to 300%
100%
*
See page
155
Torque limitation in motor mode, as a % of the rated torque.
tLIG
• [Gen. torque lim]
0 to 300%
100%
*
See page
155
Torque limitation in generator mode, as a % of the rated torque.
Ctd
• [Current threshold]
0 to 1.1 or 1.2 In (1)
according to rating
In (1)
Upper current threshold for
[I attained]
(CtA)
function assigned to a relay or a logic output (see page
91
).
CtdL
• [Low I Threshold]
0 to 1.1 or 1.2 In (1)
according to rating
0
Lower current threshold for
[Low I Th.At.]
(CtAL)
function assigned to a relay or a logic output (see page
91
).
Ftd
• [Freq. threshold]
0 to 500 or 1,000 Hz
according to rating
[Standard mot. freq]
(bFr)
Frequency threshold for
[Freq. Th. attain.]
(FtA)
function assigned to a relay or a logic output (see page
91
).
FtdL
• [Low Freq.Threshold]
0 to 500 or 1,000 Hz
according to rating
0
Lower frequency threshold for
[Low Frq. Th. Attain.]
(FtAL)
function assigned to a relay or a logic output
(see page
91
).
F2d
• [Frequency 2 threshold]
0 to 500 or 1,000 Hz
according to rating
[Standard mot. freq]
(bFr)
Frequency threshold for
[Freq. Th. 2 attain.]
(F2A)
function assigned to a relay or a logic output (see page
91
).
F2dL
• [2 Freq. Threshold]
0 to 500 or 1,000 Hz
according to rating
0
Lower frequency threshold for
[2Low F.Thld]
(F2AL)
function assigned to a relay or a logic output (see page
91
).
ttd
• [Motor therm. level]
0 to 118%
100%
*
See page
178
Trip threshold for motor thermal alarm (logic output or relay)
rtd
• [High Freq. Ref. Thr.]
0 to 500 or 1,000 Hz
according to rating
0
Upper frequency reference threshold for
[High Ref.]
(rtAH)
function assigned to a relay or a logic output
(see page
91
).
rtdL
• [Low Freq. Ref. Thr.]
0 to 500 or 1,000 Hz
according to rating
0
Lower frequency reference threshold for
[Low Ref.]
(rtAL)
function assigned to a relay or a logic output
(see page
91
).
*
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.