66
Bentone
Press
VSD
A
F
> 1 second to access login mode.
To continue with the setting work, you need to log into service engineer level. See 5.3.4.
After login is complete, continue with the setting work as shown below.
Press
or
for parameter level
000
.
Press
/reset
Display: Parameter
050
, flashes, index
00
, and value
0
do not.
/reset
7
5
4
8
z3
5
8
/1
0
0
9
Display: Parameter
bAC_UP
/reset
10.6 Backup and restore
When adjustments to the burner are complete, it is a good idea to make a
backup of the settings.
The backup ensures that the adjusted values are also saved in the display
memory. This can be useful, e.g. if there are any problems with the LMV. The
LMV can then be replaced and previous settings for the burner restored from
the display memory to the new LMV.
Backup: Means that the parameters set on the LMV control unit are saved in
the display memory.
Restore: Means that the settings saved in the display memory are
transferred to the LMV and these overwrite any settings already in the LMV.
The transferred parameter settings then act as operating parameters for the
burner.
10.6.1 Backup