79
Bentone
10.10.2 Activation of Manually OFF in operation and
adjustment of output via the display and
operating unit
When the burner is in operation position it can be set to Manually OFF which
means that the load of the burner can be manually set and will not start if the
burner is shut down.
To activate Manually OFF, first run the system to the minimum output limit.
Manual OFF can be activated by pressing
F
for at least 1 second then
LoAd 0.0
appears flashing.
Adjustment of
LoAd
can now manually be done by pressing
F
and
simultaneous pressing
or
.
The burner will now stay in set input if none of the safety regulators stops the
burner.
To deactivate and to change to automatic operation, press
ESC
for 3 seconds.
!
Manually OFF must not be used just to put a burner out of operation when doing
mounting work, or when the burner is not ready for operation. The safety notes
contained in chapter Safety notes must be observed!
!
If Manually OFF is activated, it is stored via mains OFF.
On power return, the burner assumes the Manually OFF position (OFF flashing).
!
Please note that the automatic control unit will not exit manual mode by itself.
Make sure that the automatic control unit is reset to automatic mode.
!
The unit can be changed to manual mode without login taking place. If the
automatic control unit has been left in manual mode, no automatic burner
control will take place, which in turn means that the installation is not operating
satisfactorily. For this reason, make sure when servcing/troubleshooting that the
automatic control unit is not in manual mode.