10.10 Manual output
A manual output can be set with the «Normal display» of the display and
operating unit.
10.10.1 Activation of Manually OFF in standby via
the display and operating unit
When the burner is in OFF position it can be set to Manually OFF which
means that the burner will not start.
Manual OFF can be activated by pressing
F
for at least 1 second then
LoAd 0.0
appears flashing.
LoAd 0.0
means Manually OFF.
As long as the Manual OFF is active,
OFF
appears on the normal display
flashing.
To deactivate and to change to automatic operation, press
ESC
for 3 seconds. Then OFF appears without flashing in the display.