Par
.
no.
Parameter
Number of
elements
T
ype
Edit
V
alue range
Min Max
Resolution
Default
setting
Passwor
d
level
195
Repetition limit heavy oil direct start
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
1
Std_u8
edit
1
16
1
3
SO
200
Basic unit
201
Burner operating mode (fuel train, modulating / multistage,
actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
23 = Ho mod. sep. circulation
24 = Ho 2-stage sep. circulation
25 = Ho mod. without circulation
26 = Ho 2-stage without circulation
27 = Ho 3-stage without circulation
1
Selection
edit / clear
1
27
1
undefined
SO
204
Analog output invalid (4…20 mA)
0 = default load low-fire
1 = safety sh start prevention
1
Std_u8
edit
0
1
1
1
SO
208
Program stop
0 = inactive
1 = PrePurgP
(Ph24)
2 = IgnitPos
(Ph36)
3 = interval 1
(Ph44)
4 = interval 2
(Ph52)
1
Selection
edit
0
4
1
0
SO (BA)
Summary of Contents for B 70i-3R FAME J
Page 13: ...13 Bentone 13 14 15 17 21 22 18 20 19 23 24 26 27 28 25...
Page 33: ...33 Bentone 8 2 Wiring diagram A DC Bl Svart QRB 12 11 Blue Blau Bleue Black Schwarz Noir A1...
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...