Par
.
no.
Parameter
Number of
elements
T
ype
Edit
V
alue range
Min Max
Resolution
Default
setting
Passwor
d
level
545
Lower output limit
undefined = 20 %
1
Output
edit / clear
20%
100%
0.1%
undefined
SO (BA)
546
Upper output limit
undefined = 100 %
1
Output
edit / clear
20%
100%
0.1%
undefined
SO (BA)
600
Actuators
601
Selection of reference point
Index 0 = fuel
Index 1 = air
0 = close (<0°)
1 = open (>90°)
2
Selection
edit
0
1
1
Index
0
1
Value
0
1
SO
602
Actuator’s direction of rotation
Index 0 = fuel
Index 1 = air
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
2
Selection
edit
0
1
1
Index
0
1
Value
0
1
SO
606
Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
Index 1 = air
Greatest position error where a fault is securely detected
error detection band: (parameter 606-0.6°) to
parameter 606
2
Std_u8
edit
0.5°
4°
0.1°
Index
0
1
Value
1.7°
1.7°
SO
611
Type of referencing
Index 0 = fuel
Index 1 = air
0 = standard
1 = stop within usable range
2 = internal stop (SQN1...)
3 = both
2
Std_u8
edit
0
3
1
Index
0
1
Value
0
0
SO
613
Type of actuator
Index 0 = fuel
Index 1 = air
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
2
Std_u8
edit
0
2
1
0; 0
SO
641
Control of speed standardization of VSD
Error diagnostics of negative values (refer to error code 82)
0 = no speed standardization
1 = speed standardization active
1
Std_s8
edit
-25
1
1
0
SO
642
Standardized speed
Index 0 = speed 1
Index 1 = speed 2 (internal supervision)
2
Std_u16
read only
650
6500
0.1
undefined
SO