52
Bentone
No Parameter
Actuator controlled
201
Burner operating mode (fuel train, modulating / multistage, actuators, etc.)
Air
Fuel
-- = undefined (delete curves)
•
•
1 = gas modulating (G mod)
•
•
2 = gas modulating with pilot valve (Gp1 mod)
•
•
3 = gas modulating with pilot valve (Gp2 mod)
•
•
4 = oil modulating (Lo mod)
•
•
5 = oil 2-stage (Lo 2 stage)
•
-
6 = oil 3-stage (Lo 3 stage)
•
-
7 = gas modulating (G mod pneu)
•
-
8 = gas modulating (Gp1 mod pneu)
•
-
9 = gas modulating (Gp2 mod pneu)
•
-
10 = oil modulating with gas pilot (LoGp mod)
•
•
11 = oil 2-stage with gas pilot (LoGp 2-stage)
•
-
12 = oil modulating with 2 fuel valves (Lo mod 2V)
•
•
13 = oil modulating with gas pilot and 2 fuel valves (LoGp mod 2V)
•
•
14 = gas modulating (G mod pneu, 0 active)
-
-
15 = gas modulating with pilot (Gp1 mod pneu, 0 active)
-
-
16 = gas modulating with pilot (Gp2 mod pneu, 0 active)
-
-
17 = oil 2-stage (Lo 2-stage, 0 active)
-
-
18 = oil 3-stage (Lo 3-stage, 0 active)
-
-
19 = gas modulating only when firing on gas (G mod fuel active)
-
•
20 = gas modulating with pilot only when firing on gas (Gp1 mod fuel active)
-
•
21 = gas modulating with pilot only when firing on gas (Gp2 mod fuel active)
-
•
22 = oil modulating only when firing on oil (Lo mod fuel active)
-
•
23 = HO mod with circulation
•
•
24 = HO 2-stage with circulation
•
-
25 = HO mod without circulation control
•
•
26 = HO 2-stage without circulation control
•
-
27 = HO 3-stage without circulation control
•
-
!
Ensure that the fuel train is correctly set in compliance with the type of burner
used.
Summary of Contents for B 70i-3R FAME J
Page 13: ...13 Bentone 13 14 15 17 21 22 18 20 19 23 24 26 27 28 25...
Page 33: ...33 Bentone 8 2 Wiring diagram A DC Bl Svart QRB 12 11 Blue Blau Bleue Black Schwarz Noir A1...
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...