Meaning
Valve
P0
Point of ignition (not approached in the operating
position)
V1
P1
Stage 1
V1
P2on
Switch-on point stage 2. When the angle exceeds this
point, the fuel valve for the second stage is switched on
V1
P2_d
Presetting of point P2 with no approach
V1
P2
Stage 2
V2
P2of
Switch-off point stage 2. When the angle falls below this
point, the fuel valve for the second stage is switched off
V2
P3on
Switch-on point stage 3. When the angle exceeds this
point, the fuel valve for the third stage is switched on
V2
P3_d
Presetting of point P3 with no approach
V2
P3
Stage 3
V3
P3of
Switch-off point stage 3. When the angle falls below this
point, the fuel valve for the third stage is switched off
V3
The actuator positions can be set with a resolution of 0.1°, the speeds with a
resolution of 0.1%.
10.5.2 Traveling speed
The air actuator or the VSD is operated like outside the operating position.
The defined ramp speeds are used.
The speed of the VSD can be adjusted separately for speed increase or
decrease.
No
Parameter
522
Ramp up
523
523 Ramp down
The setting also acts outside the operating position.
The running speed of the actuators is fixed at 5 seconds for a positioning
angle of 90° for SQM33.4, SQM33.5, and SQN1.
The speed is 10 seconds for a positioning angle of 90° for SQM33.6.
The SQM33.7 requires 17 seconds for a positioning angle of 90°.
Kurvpunkt
P0
P1
P2on
P2_d
P2
P2of
P3on
P3_d
P3
P3of
Summary of Contents for B 70i-3R FAME J
Page 13: ...13 Bentone 13 14 15 17 21 22 18 20 19 23 24 26 27 28 25...
Page 33: ...33 Bentone 8 2 Wiring diagram A DC Bl Svart QRB 12 11 Blue Blau Bleue Black Schwarz Noir A1...
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...