65
Bentone
When active, the Alarm in the event of start prevention function (parameter
210) is only possible to a limited extent!
The LMV37.4 system simply moves the actuators to the postpurge position.
A fan release contact cannot be controlled, as the alarm relay of the
LMV37.4 system cuts off the power supply to the outputs. With the Alarm in
the event of start prevention function, an external circuit that may be present
for controlling the fan release contact for purging in the lockout position is
activated via start prevention in standby mode.
10.5.10.7
Continuous fan
A burner can be converted into a continuous fan using conversion kit
119 230 01. See the documentation provided with the kit for instructions on
how to perform the conversion.
10.5.10.8
Continuous operation
The LMV37 automatic control unit permits continuous operation of the
burner, provided that the burner’s detector flame is an ionisation detector
flame.
When forced intermittent operation is activated, the unit shuts down for a
moment after 23 hours and 45 min of uninterrupted operation, followed by
an automatic restart.
When forced intermittent operation is inactivated the burner will run
continuously.
Forced intermittent operation is a standard feature.
279 Oil: Forced intermittent operation
0 = inactivate
1 = activated
Factory settings marked with bald text.