Err
or
code
Diagnostic
code
Meaning for the LMV37.4... system
Remedy
115
#
Internal error system counter
116
0
Designed lifecycle exceeded (250,000 startups)
Warning threshold has been reached. The unit should be replaced
117
0
Life time exceeded
Operation no longer allowed
Switch-off threshold has been reached
120
0
Interrupt limitation fuel counter input
Too many disturbance pulses at the fuel meters input
Improve EMC
121
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the p
arameter set, if error occurs
repeatedly, replace the unit
122
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the p
arameter set, if error occurs
repeatedly, replace the unit
123
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the p
arameter set, if error occurs
repeatedly, replace the unit
124
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the p
arameter set, if error occurs
repeatedly, replace the unit
125
#
Internal error EEPROM read access
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
126
#
Internal error EEPROM write access
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
127
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the p
arameter set, if error occurs
repeatedly, replace the unit
128
0
Internal error EEPROM access - synchronization during initializa
tion
Make a reset; if error occurs repeatedly, replace the unit
129
#
Internal error EEPROM access – command synchronization
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
130
#
Internal error EEPROM access - timeout
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
131
#
Internal error EEPROM access - page on abort
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
132
#
Internal error EEPROM register initialization
Make a reset; if error occurs repeatedly, replace the unit
133
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
134
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
135
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs
repeatedly, replace the unit
136
#
Restore
1
Restore started
Restore of a backup has been started (no error)
New devices require resetting following restore!
for further diagnostic codes for error code 136, refer to error code
137
For measures, refer to error code 137
137
#
Internal error – backup / restore
157 (-99)
Restore – ok, but backup < data set of current system
Restore successful, but backup data set is smaller than in the current system
239 (-17)
Backup – storage of backup in AZL2... faulty
Make reset and repeat backup
240 (-16)
Restore – no backup in AZL2...
No backup in AZL2...
Summary of Contents for B 70i-3R FAME J
Page 13: ...13 Bentone 13 14 15 17 21 22 18 20 19 23 24 26 27 28 25...
Page 33: ...33 Bentone 8 2 Wiring diagram A DC Bl Svart QRB 12 11 Blue Blau Bleue Black Schwarz Noir A1...
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...