91
7 - PARAMETER DESCRIPTION
Skip Frq Bnd
FUN 19
FUN: Skip Frq Bnd
19
0.2 Hz
LCD Display
Range
0.2 - 20.0Hz
(Default 0.2Hz)
Description
Skip Frequency band.
The Skip Frequency function is used to prevent operation of the drive at a frequency
that creates a resonant condition in the mechanical equipment associated with the motor.
Skip Frequencies are set in FUN 20-FUN 23. FUN 19 - Skip Freq Bnd sets the width of the window of
frequencies that will be skipped around the frequencies set in FUN 20-FUN 23.
When Skip Frequencies are used, the drive will accelerate or decelerate through a skip frequency, but will
not maintian speed within the skip frequency window.
Example
If FUN 19 - Skip Frq Bnd is set to 1.0 Hz, and FUN 20 - Skip Freq 1 is set to 20.0 Hz, the drive will skip
from 19.0 to 21.0 Hz.
Skip Freq 1, 2, 3, 4
FUN 20,21,22,23
FUN: Skip Freq 1
20 0.0 Hz
FUN: Skip Freq 3
22
0.0 Hz
FUN: Skip Freq 2
21
0.0 Hz
FUN: Skip Freq 4
23
0.0 Hz
LCD Display
Range
0 to Max Frequency
(Default 0.0 Hz)
Description
These parameters set the mid points of the skip frequency windows.
See also
FUN 19 - Skip Freq Bnd
Fault LO #
FUN 24
FUN: Fault LO #
24
0
LCD Display
Range
0 to 10
(Default 0)
Description
Fault Lockout Number.
This parameter sets the number of faults that may occur before automatic resetting
is
disabled. Once the number set in this parameter is exceeded, a manual reset of the fault will be required.
A manual reset is accomplished by displaying the active fault display and then pressing the [STOP] key
on the keypad or by using a digital input.
z
NOTE:
No automatic fault resets will occur if this parameter is set to 0.
See also
Fault Codes on page
to see which parameters are allowed to be auto-reset
.
The shaded parameters in
the Fault Codes are auto-resettable.
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...