13
Control Features Specifications
2 - TECHNICAL SPECIFICATIONS
2.4 Control Features Specifications
Vin1 reference input
0-5/10 Vdc, 0/4-20 mAdc (250 Ohm load) 6FS pulse train input, 0-1/10/100 kHz pulse
input, inverted function, 0-5/10 bipolar input, broken wire detection. Span and offset
adjustment.
Vin2 reference input
0-5/10 Vdc, 0-5/10 bipolar input, inverted function, broken wire detection, span and
offset adjustment. Programmable for frequency reference or current limit input
Cin reference input
0/4-20 mAdc (50 Ohm load), inverted function, span and offset adjustment.
Programmable for frequency reference or current limit input
Reference voltage
10 Vdc (10 mAdc maximum)
Digital inputs - 10
Off=0 to 3 Vdc; On=10 to 32 Vdc (pullup logic), selectable between pullup and pull
-
down logic
Digital supply voltage
24 Vdc (150 mA maximum)
Preset frequencies
3 inputs for seven preset frequencies (selectable)
Digital outputs
2 SPDT relay output - 130 Vac, 1 A/250 Vac, 0.5 A
2 open collector outputs 50 mA per device
Digital pulse train output
Open collector output pulse train proportional to output frequency
Vmet analog output
0 to 10 Vdc (5mAdc maximum)
Imet analog output
0-20 mAdc output into a 500 Ohm load (maximum)
DC holding / injection braking
At start, stop, by frequency with adjustable current level and time or
continuous DC injection by digital input.
Current limit
Four quadrant adjustable from 5 to 150%
Speed ramps
Primary and alternate adjustable from 0.1 to 3200.0 seconds
Voltage boost
Fixed boost adjustable from 0% to 50% or auto boost in vector mode
Voltage characteristic (V/Hz)
Linear, pump, fan or 2-piece linear
Timed overload
Adjustable inverse time trip (shear pin, 30 sec, 60 sec, 5 min), standard or
inverter-duty motors
Protective features
Overcurrent, overvoltage fault, ground fault, short circuit, dynamic brake
overload, drive temperature, power wiring fault, drive timed overload, input
voltage quality, overvoltage ridethrough
Program Sequence Logic
Controller (PSLC)
9-step PLC type functionally that can control speed, direction, and ramps
based on time, analog input, digital input, or pulse input
Serial Communications
Modbus Standard: RTU or ASCII
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...