147
S4 Fault Codes
8 - TROUBLESHOOTING & MAINTENANCE
8.9 S4 Fault Codes
Table below shows the fault codes that may be displayed during S4 AC drive operation, along with suggestions for
recovering from the fault condition.
When faults occur, you can access the status parameters that are saved along with the fault (Advanced Fault history).
To view these parameters, which store the drive’s status at the time of the fault, view Fault History, and select Last
Fault. Press the
Enter
key while viewing the last fault, and then use the
UP
and
DOWN
arrow keys to scroll through the
stored drive status parameters. Press the
Menu
key again to return to the programming mode fault parameter.
z
NOTE: Shaded faults are auto-resettable, except where noted.
Code Fault Display
Description
Adv.
Fault
Code
Explanation
Suggestions for Recovery
1
System
System fault
0, 1, 2
Internal microprocessor problem
Consult factory for repair or
replacement
3
Thermistor profile incorrect
Consult factory for repair or
replacement
2
EE Checksum
Checksum error
0
Memory problem when
reflashing the drive’s memory
- Reset drive to factory settings
- Consult factory
1, 2, 3
Conflict in drive’s memory
- Reset drive to factory settings
- Consult factory
4
Unable to write an EE parameter
after a parameter has been
changed through the keypad or
SIO
- Reset drive to factory settings
- Consult factory
5
The drive is receiving EE
parameter after a parameter has
been changed through the keypad
or SIO
Slow down the frequency of
Modbus writes
3
Curr Calibr
Current calibration
fault
0
Current calibration fault on phase
T1/U
- Check the motor connections to
the terminal strip of the drive
and at the motor
- Have motor checked
- Consult factory for repair or
replacement of drive
1
Current calibration fault on phase
T2/V
2
Current calibration fault on phase
T3/W
4
Power Supp
Power supply fault
0
5V supply is below 4Vdc for
more than 100ms
- Increase resistance between
REF and analog inputs
- Check wiring to REF terminals
- Consult factory
6
IOC Trip
Instantaneous
overcurrent trip
0
Short circuit was detected on
power-up
- Remove the short from the
power wiring
- Check for shorted motor
- Consult factory
7
MOL
MOL contact fault
0
The MOL digital input was
activated, depending on pull-up
or pull-down logic configuration
- Reset MOL contact or remove
condition causing the MOL
contact activation
8
Model ID
ID # out of range
0, 1, 2
Control board is not reading the
drive ID properly
Consult factory for repair or
replacement
10
Res Lockout
Restart lockout
0
The number of fault restarts is
greater than the limit defined in
FUN 24
Check the actual fault in the fault
log and use the appropriate
remedy
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...