7 - PARAMETER DESCRIPTION
DB Config
FUN 05
FUN: DB Config
05 DB Internal
LCD Display
Description
Dynamic Braking configuration.
The drive provides an internal dynamic brake resistor (DBR) to assist in
stopping. If desired, an External Braking Resistor or Bus Control System may be connected to the B-/B+
DB/DB1 terminals on the power board.
z
NOTE:
If an external DB resistor is used, it must be protected with a thermal monitor. The trip output
must be interlocked with the VFD external fault input.
See also
Dynamic Braking on page
Parameter Value
Description
No Dyn Brk
The DB circuit is disabled.
DB Internal (Default)
The VFD is set to use and protect the internal dynamic brake resistor.
DB External
An external resistor is used for additional braking capacity. The VFD will not attempt to protect this
resistor.
Int-ARCTIC
Dynamic braking becomes active if the drive temperature drops below -7 degrees C. ARCTIC Mode
•
warning flashes on the keypad when the DB becomes active. The drive will be disabled and not
allowed to run if the drive drops below -10 degrees C. The keypad will indicate a “Not Enabled”
state at this point. The drive must meet the following criteria before operating again.
Drive temperature must be above -9 degrees C, and
•
Drive temperature must stay above -9 degrees
C until a time period has elapsed. The time period is dependent on how far below -10 degrees C the
drive was. Each degree below -10 degrees C adds another 4 minutes before restart.
The VFD can operate down to -15 degrees C with no wind loading in Artic Mode
•
Range
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...