55
5 - KEYPAD OPERATION AND PROGRAMMING
5.6.2 S4 Keypad Status Messages
S4 Keypad Status Messages
Message
Meaning
Stopped
The drive is not spinning the motor or injecting DC voltage. The drive is ready
to run when given the proper signal.
FWD Accel
The drive is spinning the motor in the forward direction and the speed of the
motor is increasing.
REV Accel
The drive is spinning the motor in the reverse direction and the speed of the
motor is increasing.
FWD Decel
The drive is spinning the motor in the forward direction and the speed of the
motor is decreasing.
REV Decel
The drive is spinning the motor in the reverse direction and the speed of the
motor is decreasing.
Jog FWD
The drive is jogging in the forward direction.
Jog REV
The drive is jogging in the reverse direction.
FWD At Spd
The drive is spinning the motor in the forward direction and the speed of the
motor is at the reference frequency.
REV at Spd
The drive is spinning the motor in the reverse direction and the speed of the
motor is at the reference frequency.
Zero Speed
The drive has an active run signal but the motor is not spinning because the
reference speed to the drive must be 0.0 Hz, or the drive is in sleep mode..
DC Inject Faulted
The drive is injecting DC voltage into the motor.
Faulted
The drive is faulted.
Reset-Fit
The drive is faulted, but has the possibility of being automatically reset.
LS Lockout
Line-Start Lockout functionality has become active. This means there was an
active run signal during power-up or when a fault was reset. This run signal
must be removed before the Line-Start Lockout functionality will be removed.
Catch Fly
The Catch on the Fly functionality is actively searching for the motor frequency.
Forward
The drive is running forward without accelerating, decelerating or residing at the
reference frequency. This means that something is keeping the drive from the
reference frequency.
Reverse
The drive is running in reverse without accelerating, decelerating or residing at
the reference frequency. This means that something is keeping the drive from the
reference frequency.
Not Enabled
The drive is not allowed to run because the digital input enable (EN) is not active or
because ARCTIC mode has shut down the run operation.
Volt Range
The drive has not met the input voltage requirements that it needs to be able to
run. In other words, the Bus Voltage of the drive is either too low or too high.
Low Voltage
The drive has reached an undervoltage state.
Kpd Stop
A stop command was given from the keypad when the keypad was not the active
control source. To remove this condition, the run signal to the drive must be
removed.
ARCTIC Mode
The ARCTIC DB Resistor mode is actively pulsing the DB
Resistor
Mtr Measure
An RS Measurement is armed or active
IR Active
Valid IR communications are occurring
Seq Running
The program sequencer functionality is active
Summary of Contents for RSi S4 Series
Page 4: ......
Page 9: ...1 1 Introduction...
Page 16: ...8 1 INTRODUCTION NOTES...
Page 17: ...9 2 Technical Specifications...
Page 28: ...20 2 TECHNICAL SPECIFICATIONS NOTES...
Page 29: ...21 3 Installation...
Page 37: ...29 4 Connections...
Page 51: ...43 4 CONNECTIONS 4 5 2 S4 Wiring Diagram S4 Series Wiring Diagram...
Page 56: ...48 4 CONNECTIONS NOTES...
Page 57: ...49 5 Keypad Operation and Programming...
Page 70: ...62 NOTES 5 KEYPAD OPERATION AND PROGRAMMING...
Page 71: ...63 6 Parameter Groups...
Page 82: ...74 NOTES 6 S4 Parameter Groups...
Page 83: ...75 7 Parameter Descriptions...
Page 149: ...141 8 Troubleshooting Maintenance...
Page 159: ...151 9 Motor Characteristics...
Page 162: ...154 9 MOTOR CHARACTERISTICS NOTES...
Page 163: ...155 10 Options...
Page 165: ...157 11 Appendices...