RS7580V-601 Rotary-Screw Air Compressor
19
P/N 5900090 — Rev. A — Sept. 2019
Connect to a Power Source
The Compressor must be connected to an appropriate power source.
⚠
DANGER
All electrical work
must be done by a licensed, certified Electrician
in
accordance with all applicable local electrical codes
. Damage caused by improper
electrical installation may void your warranty.
All electrical work
must
conform to applicable local, state, and federal codes, rules, and regulations,
such as state and federal OSHA regulations and electrical codes. The Compressor
must
be
grounded.
Important
: BendPak recommends having your Electrician check all wire connections inside the
Electrical Box; sometimes they can become loose during transport.
Based on what’s best for your specific location, most customers have their Electrician:
•
Wire the Compressor directly into the facility’s electrical system, or
•
Add a power cord with appropriate plug to the Compressor, which is then plugged in to an
appropriate power source.
The Electrician will need to provide these components; they are
not
supplied with the Compressor.
There is a hole in the bottom of the Electrical Box (labelled
Power In
on the inside) specifically for
wiring the Compressor to a power source.
Important
:
The Compressor uses electrical energy and creates pneumatic energy; if your
organization has Lockout/Tagout policies, make sure to implement them after
connecting the Compressor to a power source.
The Compressor’s motor is 7.5 horsepower, 208-240 VAC, 50 or 60 Hz, 1 phase. BendPak
recommends using a 60 Amp breaker and 6 AWG (if the 60 Amp breaker trips frequently, switch to a
higher breaker until the tripping stops) .
Check the ID plate for additional information
.
This drawing on the next page uses the United States color codes for the three wires that need to be
connected inside the Compressor’s Electrical Box:
•
Black
: Live
•
White
: Live
•
Green
: Ground
If you are using the Compressor in Europe, the Black – White – Green colors correspond to:
•
Brown
: Live
•
Blue
: Neutral
•
Green/Yellow
: Ground
Information about color code conventions in other regions and countries is available online.
To connect the Compressor to a power source
:
1.
Work with the Electrician to decide whether you are going to wire the Compressor into the facility’s
electrical system or connect a power cord with appropriate plug.
2.
Have your Electrician get the necessary components.
3.
Route the wiring through the hole in the bottom of the Electrical Box.
The wiring needs to have three wires, Black-White-Green in the United States.
Summary of Contents for RS7580V-601
Page 37: ...RS7580V 601 Rotary Screw Air Compressor 37 P N 5900090 Rev A Sept 2019 Wiring Diagram...
Page 38: ...RS7580V 601 Rotary Screw Air Compressor 38 P N 5900090 Rev A Sept 2019 Labels...
Page 39: ...RS7580V 601 Rotary Screw Air Compressor 39 P N 5900090 Rev A Sept 2019...
Page 40: ...RS7580V 601 Rotary Screw Air Compressor 40 P N 5900090 Rev A Sept 2019...
Page 43: ...RS7580V 601 Rotary Screw Air Compressor 43 P N 5900090 Rev A Sept 2019 Maintenance Log...