4–51
System Setup and Setpoints – 4
24 Volts/Hz Overexcitation
NOTE:
Two or four voltage inputs are available
for the M-3311A. The Voltage Input can
be a phase voltage input or voltage
generated from a broken delta VT con
-
nection. 81O/U, 27, and 24 Functions
are only available if the voltage input is
connected to the phase voltage. If the
voltage input is connected to phase volt-
age, Function 59G will be unavailable.
Function 59G is only available if the
voltage input is connected to a broken
delta VT. If voltage input is connected to
broken delta VT, Functions 81O/U, 27,
and 24 will be unavailable.
The 24 Volts-Per-Hertz (V/Hz) function provides
over-excitation protection for the transformer. As the
volts per hertz level rises above a transformer’s limit,
leakage flux increases. The leakage flux induces
current in the transformer support structure causing
rapid localized heating.
In power plant applications, over-excitation can
occur due to sudden tripping of the generator as a
result of faults and other abnormal conditions.
In Extra High Voltage (EHV) applications, an incor
-
rectly switched line can lead to over-excitation at
tapped transformers due to combined capacitance.
In transmission and distribution applications, sud-
den loss of load or improper capacitor/reactor
switching may result in overexcitation.
This function provides two Definite Operating Time
setpoints, four families of Inverse Time curves widely
used in the industry (see Appendix D, Figures D1 to
D4), and a linear reset rate programmable to match
specific cooling characteristics of the transformer.
The V/Hz function provides reliable measurements
of V/Hz for a frequency range of 10–80 Hz.
When applied for generator and unit transformer
protection, the first task in setting this relay function
is to determine the desired protective levels and
times. This can be accomplished by combining the
V/Hz limit curves of the transformer and the associ
-
ated generator on one graph and simplifying the re-
sult into one curve to coordinate with the protection.
Example of Transformer limits:
• Full Load V/Hz = 1.05 PU (HV terminals)
• No Load V/Hz = 1.10 PU (HV terminals)
NOTE:
The curves must be on the same volt-
age base to be combined on one graph.
An example is shown in Figure 4-28,
Example of Capability and Protection
Curves. The manufacturer of the genera-
tor and transformer will provide these
over-excitation capability limits.
Depending on these characteristics, they can best
be matched by one of the four families of inverse
time curves, alone or in conjunction with definite
time setpoints. Coordination of capabilities and
protection is achieved when the time between the
relay operation and the capability limit is sufficient
for the breakers to open and de-energize the units.
This coordination time is read vertically between
the two curves at any given V/Hz value.
Figure 4-28, Example of Capability and Protection
Curves, illustrates a composite graph of gen-
erator limits, transformer limits, a chosen inverse
time curve, inverse time pickup, and definite time
setpoint. While inverse time curve selection may
provide more selective and sensitive protection,
a traditional two-step protection scheme may be
realized by using the two definite time functions
(24DT #1 and #2), and disabling the inverse (24IT)
element.
Summary of Contents for M?3311A
Page 1: ...Instruction Book M 3311A Transformer Protection Relay ...
Page 30: ... 29 M 3311A Transformer Protection Relay This Page Left Intentionally Blank ...
Page 55: ...M 3311A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 87: ...M 3311A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 89: ...M 3311A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 107: ...M 3311A Instruction Book 3 20 Figure 3 22 Setup System Dialog Screen 2 3 Winding ...
Page 108: ...IPScom 3 3 21 Figure 3 23 Setup System Dialog Screen 4 Winding ...
Page 112: ...IPScom 3 3 25 Figure 3 29 I O Map Screen 4 Winding ...
Page 114: ...IPScom 3 3 27 Figure 3 31 Display All Setpoints Screen 4 Winding ...
Page 119: ...M 3311A Instruction Book 3 32 Figure 3 38 View Sequence of Events Recorder Screen ...
Page 127: ...M 3311A Instruction Book 3 40 This Page Left Intentionally Blank ...
Page 150: ...4 23 System Setup and Setpoints 4 Figure 4 14 Setup Sequence of Events Recorder Dialog Screen ...
Page 163: ...4 36 M 3311A Instruction Book Figure 4 15 IPScom Relay Setup System Dialog Screen 2 3 Winding ...
Page 166: ...4 39 System Setup and Setpoints 4 Figure 4 18 IPScom Selection Screen for Input Settings ...
Page 179: ...4 52 M 3311A Instruction Book Figure 4 28 Example of V Hz Capability and Protection Curves ...
Page 187: ...4 60 M 3311A Instruction Book Figure 4 33 49 Function Overload Curves ...
Page 229: ...4 102 M 3311A Instruction Book Table 4 5 Transformer Connections ...
Page 231: ...4 104 M 3311A Instruction Book Table 4 7 Custom Transformer and CT Configuration ...
Page 243: ...M 3311A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 383: ...A 50 M 3311A Instruction Book This Page Left Intentionally Blank ...
Page 389: ...M 3311A Instruction Book B 6 This Page Left Intentionally Blank ...
Page 393: ...D 2 M 3311A Instruction Book Figure D 1 Volts Hz 24IT Inverse Curve Family 1 Inverse Square ...
Page 394: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24IT Inverse Family Curve 2 ...
Page 395: ...D 4 M 3311A Instruction Book Figure D 3 Volts Hz 24IT Inverse Time Curve Family 3 ...
Page 396: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 399: ...D 8 M 3311A Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 400: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 401: ...D 10 M 3311A Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 402: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 439: ...F 28 M 3311A Instruction Book This Page Left Intentionally Blank ...