4–22
M‑3311A Instruction Book
IPScom
Setup Sequence of Events Recorder
Protective function Pickup, Trip, Dropout and/or Out-
put/Input Pickup or Dropout are selected to trigger
the Sequence of Events Recorder.
NOTE
: Communication must be established with
the target relay for this procedure. When
not connected to the relay the Save se-
lection does not save the Sequence of
Event settings to the open file.
To setup the Sequence of Events Recorder perform
the following:
1.
From the IPScom Main Screen menu
select
Relay/Sequence of Events/
Setup
. IPScom will display the Setup
Sequence of Events Recorder dialog
screen (Figure 4-14).
2.
Select the desired Inputs and Outputs,
then select
Save
. IPScom will display
a save to device confirmation (Figure
4-2).
3. Select
YES
, IPScom will return to the
Main Screen.
HMI Setup Through Fault Recorder
The Through Fault Recorder captures separate
Through Faults. Each Through Fault record contains
the serial number of the fault, duration of the event,
maximum RMS fault current magnitude for each
phase during the fault, I
2
t and the time stamp of the
fault. In addition, it will also store the total number
of through faults since last rest and total I
2
t for each
phase since lase reset (up to 256 records).
To Setup the relay Through Fault recorder perform
the following:
1.
Press the
ENTER
pushbutton.
2.
If Level Access is active, the following is
displayed:
ENTER ACCESS CODE
0
a. Input the required Access Code, then
press
ENTER
.
b. If the proper Access Code has been
entered, the HMI will return:
LEVEL #(1,2 or 3)
Access Granted!
VOLTAGE RELAY
VOLT curr freq v/hz
c. Go to step 4.
3.
If Level Access is not active, then the
following is displayed:
VOLTAGE RELAY
VOLT curr freq v/hz
4.
Press the Right arrow pushbutton until
the following is displayed:
THROUGH FAULT
ips brkr THFLT tcm
5. Press
ENTER
, the following will be dis
-
played:
THFLT CURRENT THRESHOLD
__
Amps
6.
Utilizing the Up or Down arrow push
-
button set the Through Fault Current
Threshold setting, then press
ENTER
,
the following is displayed:
THFLT CUM. I^2T LIMIT
__ kA^2-cycles
7.
Utilizing the Up or Down arrow pushbut
-
ton set the Through Fault Cumulative
i^2t Limit setting, then press
ENTER
,
the following is displayed:
THFLT PU OPERATIONS LIM.
__ Records
8.
Utilizing the Up or Down arrow pushbut
-
ton set the Through Fault PU Operations
Limit setting, then press
ENTER
, the
following is displayed:
THFLT WINDING SELECT
sum1 sum2 w1 w2 w3 w4
Summary of Contents for M?3311A
Page 1: ...Instruction Book M 3311A Transformer Protection Relay ...
Page 30: ... 29 M 3311A Transformer Protection Relay This Page Left Intentionally Blank ...
Page 55: ...M 3311A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 87: ...M 3311A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 89: ...M 3311A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 107: ...M 3311A Instruction Book 3 20 Figure 3 22 Setup System Dialog Screen 2 3 Winding ...
Page 108: ...IPScom 3 3 21 Figure 3 23 Setup System Dialog Screen 4 Winding ...
Page 112: ...IPScom 3 3 25 Figure 3 29 I O Map Screen 4 Winding ...
Page 114: ...IPScom 3 3 27 Figure 3 31 Display All Setpoints Screen 4 Winding ...
Page 119: ...M 3311A Instruction Book 3 32 Figure 3 38 View Sequence of Events Recorder Screen ...
Page 127: ...M 3311A Instruction Book 3 40 This Page Left Intentionally Blank ...
Page 150: ...4 23 System Setup and Setpoints 4 Figure 4 14 Setup Sequence of Events Recorder Dialog Screen ...
Page 163: ...4 36 M 3311A Instruction Book Figure 4 15 IPScom Relay Setup System Dialog Screen 2 3 Winding ...
Page 166: ...4 39 System Setup and Setpoints 4 Figure 4 18 IPScom Selection Screen for Input Settings ...
Page 179: ...4 52 M 3311A Instruction Book Figure 4 28 Example of V Hz Capability and Protection Curves ...
Page 187: ...4 60 M 3311A Instruction Book Figure 4 33 49 Function Overload Curves ...
Page 229: ...4 102 M 3311A Instruction Book Table 4 5 Transformer Connections ...
Page 231: ...4 104 M 3311A Instruction Book Table 4 7 Custom Transformer and CT Configuration ...
Page 243: ...M 3311A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 383: ...A 50 M 3311A Instruction Book This Page Left Intentionally Blank ...
Page 389: ...M 3311A Instruction Book B 6 This Page Left Intentionally Blank ...
Page 393: ...D 2 M 3311A Instruction Book Figure D 1 Volts Hz 24IT Inverse Curve Family 1 Inverse Square ...
Page 394: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24IT Inverse Family Curve 2 ...
Page 395: ...D 4 M 3311A Instruction Book Figure D 3 Volts Hz 24IT Inverse Time Curve Family 3 ...
Page 396: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 399: ...D 8 M 3311A Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 400: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 401: ...D 10 M 3311A Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 402: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 439: ...F 28 M 3311A Instruction Book This Page Left Intentionally Blank ...