M‑3311A Instruction Book
6–10
6.3
Automatic Calibration
The M-3311A Transformer Protection Relay has
been fully calibrated at the factory. There is no need
to recalibrate the unit prior to installation. Further
calibration is only necessary if a component was
changed.
For units equipped with an optional M-3931 HMI:
8
WARNING: All relay functions and protection
will be inoperative while the relay is in
Diagnostic Mode.
1. Navigate to the
Auto Calibration
function in the
Diagnostic Mode
menu.
The following is displayed:
AUTO CALIBRATION
com3 clock led CAL
2. Press
ENTER
. The following is displayed:
CONNECT REFERENCE INPUTS
PRESS ENTER TO CALIBRATE
3. Connect voltage inputs in parallel to
terminal 36,64 (neutral) and terminal
37,65 (hot) and apply 120.00 (
0.01)
VAC
s
0°.
Hot
Neutral
37
36
Voltage
Input
120 V ac 0
o
V
2
V
1
65
64
Figure 6-7 Voltage Calibration Configuration
(4 Winding)
4. Connect all current inputs in series (
I
A
W
1
=
I
B
W
1
=
I
C
W
1
=
I
A
W
2
=
I
B
W
2
=
I
C
W
2
=
I
G
W
2
=
I
A
W
3
=
I
B
W
3
=
I
C
W
3
=
I
G
W
3
=
I
A
W
4
=
I
B
W
4
=
I
C
W
4
=
I
G
W
4
)
5.
Apply 5.00 (
0.01) Amps
s
0°. For 1
Amp CT models, use 1.0 (
0.01) Amps
s
0°.
+
Current
Input
41
40
39
38
43
42
45
44
47
46
49
48
51
50
53
52
55
54
57
56
59
58
I
A
W
1
I
B
W
1
I
C
W
1
I
A
W
2
I
B
W
2
I
C
W
2
I
G2
W
2
I
A
W
3
I
B
W
3
I
C
W
3
I
G3
W
2
-
67
66
I
A
W
4
69
68
I
B
W
4
71
70
I
C
W
4
73
72
I
G
W
4
Figure 6-8 Current Calibration Configuration
(4 Winding)
6. Press
ENTER
to start calibration. While the
unit is calibrating, the display will show:
AUTO CALIBRATION
-WAIT-
7. When the calibration is complete, unit
will display:
AUTO CALIBRATION
-DONE-
8. The calibration can be verified by reading the
Status (see the
Monitor Status
menu, and
Monitor Status/Metering in Chapter 3).
For units without the optional M-3931 HMI:
It is possible to autocalibrate M-3311A units that
are not equipped with the optional M-3931 HMI. The
procedure is similar to HMI equipped units:
1. Remove power from the unit.
2. Place unit in calibrate mode by configuring
the proper dip switches (see Table 5-2).
3. Connect voltage inputs.
4. Connect all current inputs in series.
5. Apply power to the unit. The
DIAG
LED
will illuminate when operation is complete.
6. Remove power from the unit, then return
dip switches to
RUN
position.
Summary of Contents for M?3311A
Page 1: ...Instruction Book M 3311A Transformer Protection Relay ...
Page 30: ... 29 M 3311A Transformer Protection Relay This Page Left Intentionally Blank ...
Page 55: ...M 3311A Instruction Book 1 6 This Page Left Intentionally Blank ...
Page 87: ...M 3311A Instruction Book 2 32 This Page Left Intentionally Blank ...
Page 89: ...M 3311A Instruction Book 3 2 Figure 3 2 IPScom Main Screen ...
Page 107: ...M 3311A Instruction Book 3 20 Figure 3 22 Setup System Dialog Screen 2 3 Winding ...
Page 108: ...IPScom 3 3 21 Figure 3 23 Setup System Dialog Screen 4 Winding ...
Page 112: ...IPScom 3 3 25 Figure 3 29 I O Map Screen 4 Winding ...
Page 114: ...IPScom 3 3 27 Figure 3 31 Display All Setpoints Screen 4 Winding ...
Page 119: ...M 3311A Instruction Book 3 32 Figure 3 38 View Sequence of Events Recorder Screen ...
Page 127: ...M 3311A Instruction Book 3 40 This Page Left Intentionally Blank ...
Page 150: ...4 23 System Setup and Setpoints 4 Figure 4 14 Setup Sequence of Events Recorder Dialog Screen ...
Page 163: ...4 36 M 3311A Instruction Book Figure 4 15 IPScom Relay Setup System Dialog Screen 2 3 Winding ...
Page 166: ...4 39 System Setup and Setpoints 4 Figure 4 18 IPScom Selection Screen for Input Settings ...
Page 179: ...4 52 M 3311A Instruction Book Figure 4 28 Example of V Hz Capability and Protection Curves ...
Page 187: ...4 60 M 3311A Instruction Book Figure 4 33 49 Function Overload Curves ...
Page 229: ...4 102 M 3311A Instruction Book Table 4 5 Transformer Connections ...
Page 231: ...4 104 M 3311A Instruction Book Table 4 7 Custom Transformer and CT Configuration ...
Page 243: ...M 3311A Instruction Book 5 6 Figure 5 5 Mounting Dimensions for GE L 2 Cabinet H3 and H4 ...
Page 383: ...A 50 M 3311A Instruction Book This Page Left Intentionally Blank ...
Page 389: ...M 3311A Instruction Book B 6 This Page Left Intentionally Blank ...
Page 393: ...D 2 M 3311A Instruction Book Figure D 1 Volts Hz 24IT Inverse Curve Family 1 Inverse Square ...
Page 394: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24IT Inverse Family Curve 2 ...
Page 395: ...D 4 M 3311A Instruction Book Figure D 3 Volts Hz 24IT Inverse Time Curve Family 3 ...
Page 396: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 399: ...D 8 M 3311A Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 400: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 401: ...D 10 M 3311A Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 402: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 439: ...F 28 M 3311A Instruction Book This Page Left Intentionally Blank ...